Energy and Carbon Savings in Data Centres Through Liquid-to-Chip Cooling with Differential Temperature Control

• Converting data centres from air-to-chip (ATC), to liquid-to-chip (LTC) could reduce peak energy demand per kWhr of compute by 6%–14% • Annual energy consumption, carbon emissions, and power usage efficiency (PUE) may be improved by 4%–13% per kWhr of compute by data centre conversion from ATC to LTC • Increasing fluid differential and supply temperatures for LTC systems can eliminate the need for high energy use refrigerant compressor chillers in Australian and Asian climates. • Applying the novel control method to increase fluid differential temperatures from 5°C to 10°C based on I.T. kW measurement for LTC data centres could improve total data centre efficiency between approximately 3%∼6%, reduce PUE from a range of 1.22∼1.25 to 1.18 and potentially reduce central plant energy 18∼28%. The rapid and large-scale development of data centres to manage computational demand is resulting in potential strain on electrical energy and water utilities globally. New methods for minimising the peak power demand and annual energy of data centres that can be adapted to the different ambient conditions of various geographic locations are urgently needed. This study applies a novel advanced method of energy savings by differential temperature control via I.T. kW load measurement, to the conversion of data centres from conventional air-to-chip (ATC) cooling, to new liquid-to-chip (LTC) cooling. The novel method potentially assists elimination of energy-intensive chillers in favour of free cooling, reduces peak power demand and annual energy consumption for temperate to tropical ambient conditions. A new energy model was developed in Design Builder TM and EnergyPlus TM and was validated by onsite measurements at a state-of-the-art data centre in Melbourne, Australia and utilised to predict and optimize the improvement in energy efficiency by controlling differential temperature. The results indicate that converting from ATC cooling to LTC cooling could reduce the total peak power demand by 6%∼14% and reduce the annual energy consumption, carbon emissions and power usage efficiency by 4%∼13%. Application of the advanced control method to increase differential temperature from 5°C to 10°C for LTC systems, predicted reduction of the PUE from a range of 1.22∼1.25 to 1.18, potentially contributing an 18∼28% reduction in central plant energy.

Authors

Institutions

Publication Details

Journal
Advances in Applied Energy
Published
2026-03-01
DOI
https://doi.org/10.1016/j.adapen.2026.100269
Primary Topic
Heat Transfer and Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Energy and Carbon Savings in Data Centres Through Liquid-to-Chip Cooling with Differential Temperature Control

Michael E. Cholette, Jeffrey Daniel Van Zetten, Keivan Bamdad
Advances in Applied Energy
Heat Transfer and Optimization
article

Energy and Carbon Savings in Data Centres Through Liquid-to-Chip Cooling with Differential Temperature Control

Michael E. Cholette, Jeffrey Daniel Van Zetten, Keivan Bamdad
article en

Abstract

• Converting data centres from air-to-chip (ATC), to liquid-to-chip (LTC) could reduce peak energy demand per kWhr of compute by 6%–14% • Annual energy consumption, carbon emissions, and power usage efficiency (PUE) may be improved by 4%–13% per kWhr of compute by data centre conversion from ATC to LTC • Increasing fluid differential and supply temperatures for LTC systems can eliminate the need for high energy use refrigerant compressor chillers in Australian and Asian climates. • Applying the novel control method to increase fluid differential temperatures from 5°C to 10°C based on I.T. kW measurement for LTC data centres could improve total data centre efficiency between approximately 3%∼6%, reduce PUE from a range of 1.22∼1.25 to 1.18 and potentially reduce central plant energy 18∼28%. The rapid and large-scale development of data centres to manage computational demand is resulting in potential strain on electrical energy and water utilities globally. New methods for minimising the peak power demand and annual energy of data centres that can be adapted to the different ambient conditions of various geographic locations are urgently needed. This study applies a novel advanced method of energy savings by differential temperature control via I.T. kW load measurement, to the conversion of data centres from conventional air-to-chip (ATC) cooling, to new liquid-to-chip (LTC) cooling. The novel method potentially assists elimination of energy-intensive chillers in favour of free cooling, reduces peak power demand and annual energy consumption for temperate to tropical ambient conditions. A new energy model was developed in Design Builder TM and EnergyPlus TM and was validated by onsite measurements at a state-of-the-art data centre in Melbourne, Australia and utilised to predict and optimize the improvement in energy efficiency by controlling differential temperature. The results indicate that converting from ATC cooling to LTC cooling could reduce the total peak power demand by 6%∼14% and reduce the annual energy consumption, carbon emissions and power usage efficiency by 4%∼13%. Application of the advanced control method to increase differential temperature from 5°C to 10°C for LTC systems, predicted reduction of the PUE from a range of 1.22∼1.25 to 1.18, potentially contributing an 18∼28% reduction in central plant energy.

Advances in Applied Energy
Queensland University of Technology (AU), Western Sydney University (AU)
Affordable and clean energy
Openalex Percentile: Top 8%
Heat Transfer and Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.