Investigation on DC interruption characteristics of three-electrode vacuum interrupter under Halbach transverse magnetic fields

• The three-electrode vacuum interrupter enables magnetically driven arc transfer. • Halbach transverse magnetic field guides the arc to the annular third electrode. • Complete arc transfer enables capacitor-assisted DC commutation. • Fast interruption achieved: 1000 V/920 A in 0.53 ms and 450 V/400 A in 2.35 ms. • Arc-transfer mode strongly depends on capacitor precharge and fault current level. A vacuum interrupter is the core component of a direct current (DC) circuit breaker, but DC interruption is challenging because there is no natural current zero. This paper investigates an arc-transfer DC interruption approach enabled by an annular Halbach transverse magnetic field and a three-electrode vacuum interrupter. An eight-magnet Halbach array provides a magnetic field exceeding 400 mT, which drives arc migration. Under a transverse magnetic field, the DC arc shows voltage oscillations, and the arc voltage can exceed the supply voltage, reaching 1.6 kV, which promotes current extinction. At high current, the arc can attach to the shield when the initial current exceeds 1 kA. Based on this phenomenon, the internal shield is redesigned as an insulated lead-out shield electrode along the migration path, connected to a precharged capacitor auxiliary branch. After the arc attaches to the lead-out shield electrode, the precharged pulse capacitor discharges into the auxiliary branch, generating an oscillatory current that forces a current zero and enables interruption independent of the main gap. Experiments demonstrate interruption of 1000 V and 920 A within 0.53 ms. The proposed three-electrode concept features a simple structure and a passive commutation interface, offering reliability and cost-effectiveness for DC interruption.

Publication Details

Journal
Electric Power Systems Research
Published
2026-03-24
DOI
https://doi.org/10.1016/j.epsr.2026.113007
Primary Topic
Vacuum and Plasma Arcs
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Investigation on DC interruption characteristics of three-electrode vacuum interrupter under Halbach transverse magnetic fields

Electric Power Systems Research
Vacuum and Plasma Arcs
article

Investigation on DC interruption characteristics of three-electrode vacuum interrupter under Halbach transverse magnetic fields

article en

Abstract

• The three-electrode vacuum interrupter enables magnetically driven arc transfer. • Halbach transverse magnetic field guides the arc to the annular third electrode. • Complete arc transfer enables capacitor-assisted DC commutation. • Fast interruption achieved: 1000 V/920 A in 0.53 ms and 450 V/400 A in 2.35 ms. • Arc-transfer mode strongly depends on capacitor precharge and fault current level. A vacuum interrupter is the core component of a direct current (DC) circuit breaker, but DC interruption is challenging because there is no natural current zero. This paper investigates an arc-transfer DC interruption approach enabled by an annular Halbach transverse magnetic field and a three-electrode vacuum interrupter. An eight-magnet Halbach array provides a magnetic field exceeding 400 mT, which drives arc migration. Under a transverse magnetic field, the DC arc shows voltage oscillations, and the arc voltage can exceed the supply voltage, reaching 1.6 kV, which promotes current extinction. At high current, the arc can attach to the shield when the initial current exceeds 1 kA. Based on this phenomenon, the internal shield is redesigned as an insulated lead-out shield electrode along the migration path, connected to a precharged capacitor auxiliary branch. After the arc attaches to the lead-out shield electrode, the precharged pulse capacitor discharges into the auxiliary branch, generating an oscillatory current that forces a current zero and enables interruption independent of the main gap. Experiments demonstrate interruption of 1000 V and 920 A within 0.53 ms. The proposed three-electrode concept features a simple structure and a passive commutation interface, offering reliability and cost-effectiveness for DC interruption.

Electric Power Systems ResearchVol. 257
Openalex Percentile: Top 9%
Vacuum and Plasma Arcs
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.