Analysis on the causes of high lightning trip-out rate on electric transmission lines

• According to the findings presented in this article, when the lightning strikes the center of overhead ground wire between two towers, the assumption of a reflection coefficient of -1 specified in engineering practice is not entirely accurate. It is recommended that this situation be modified. • In deep canyon regions, thunderclouds may pass beneath high-voltage transmission lines, thereby creating conditions conducive to lightning strikes on these lines. • Traditional two-dimensional and three-dimensional are inapplicable or need adaptation for this deep canyon topography. The specific reasons are as described in Chapter 3 of this article. The causes of frequent lightning trip-out on transmission lines are complex and involve multiple interacting factors. In particular, high-voltage long-distance transmission lines operating in complex terrains are exposed to a markedly higher risk of lightning-induced outages. In this study, a wave reflection analysis is employed to investigate lightning performance under high soil resistivity conditions. The results indicate that when a lightning strike occurs at the midpoint of the overhead ground wire between two adjacent towers, the air gap between the overhead ground wire and the phase conductor becomes highly susceptible to back-flashover overvoltage, leading to localized flashover. Furthermore, a modified electrogeometric model tailored for canyon terrains is proposed and applied to representative engineering cases. The analysis shows that the risk of lightning shielding failure for high-voltage transmission lines in canyon areas increases significantly when canyon-depth effects are taken into account. These findings highlight that complex site conditions, such as high soil resistivity and canyon topography, should be explicitly considered in the lightning protection design of high-voltage long-distance transmission lines.

Authors

Institutions

Publication Details

Journal
Results in Engineering
Published
2026-03-13
DOI
https://doi.org/10.1016/j.rineng.2026.110083
Primary Topic
Lightning and Electromagnetic Phenomena
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Analysis on the causes of high lightning trip-out rate on electric transmission lines

Jufeng Wang, Jieting Bi
Results in Engineering
Lightning and Electromagnetic Phenomena
article

Analysis on the causes of high lightning trip-out rate on electric transmission lines

Jufeng Wang, Jieting Bi
article en

Abstract

• According to the findings presented in this article, when the lightning strikes the center of overhead ground wire between two towers, the assumption of a reflection coefficient of -1 specified in engineering practice is not entirely accurate. It is recommended that this situation be modified. • In deep canyon regions, thunderclouds may pass beneath high-voltage transmission lines, thereby creating conditions conducive to lightning strikes on these lines. • Traditional two-dimensional and three-dimensional are inapplicable or need adaptation for this deep canyon topography. The specific reasons are as described in Chapter 3 of this article. The causes of frequent lightning trip-out on transmission lines are complex and involve multiple interacting factors. In particular, high-voltage long-distance transmission lines operating in complex terrains are exposed to a markedly higher risk of lightning-induced outages. In this study, a wave reflection analysis is employed to investigate lightning performance under high soil resistivity conditions. The results indicate that when a lightning strike occurs at the midpoint of the overhead ground wire between two adjacent towers, the air gap between the overhead ground wire and the phase conductor becomes highly susceptible to back-flashover overvoltage, leading to localized flashover. Furthermore, a modified electrogeometric model tailored for canyon terrains is proposed and applied to representative engineering cases. The analysis shows that the risk of lightning shielding failure for high-voltage transmission lines in canyon areas increases significantly when canyon-depth effects are taken into account. These findings highlight that complex site conditions, such as high soil resistivity and canyon topography, should be explicitly considered in the lightning protection design of high-voltage long-distance transmission lines.

Results in EngineeringVol. 30
Guangxi University (CN), Guangxi Zhuang Autonomous Region Department of Education (CN), Jiangsu Vocational College of Medicine (CN), Guangxi Zhuang Autonomous Region Health and Family Planning (CN)
Affordable and clean energy
Openalex Percentile: Top 27%
Lightning and Electromagnetic Phenomena
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.