Comparative Thermal Analysis of Sleeve Connection Methods for Aluminum and Copper Conductors

Aluminum conductors are used in overhead transmission lines, while copper is used in underground and submarine cables. This study analyzed thermal characteristics of compression, bolted, and welded sleeves for aluminum, and compression and bolted sleeves for copper. Conductive compound and moisture compound removal effects on sleeve heating were evaluated under varying conditions. Thermal cycling tests per ANSI C119.4 and C119.0 standards (60-90℃) measured temperature differences between sleeves and reference conductors. Statistical analysis using Weibull and normal distributions showed bolted connection had best performance. Conductive compound applied with two outer moisture layers removed showed the lowest temperature. Similar patterns were observed at 600 A for aluminum and 900 A for copper, confirming aluminum's lower conductivity affects heating. Results provide baseline data for evaluating 70 kV aluminum underground and submarine cable joints..

Authors

Publication Details

Journal
The Transactions of The Korean Institute of Electrical Engineers
Published
2026-03-13
DOI
https://doi.org/10.5370/kiee.2026.75.3.577
Primary Topic
Electronic Packaging and Soldering Technologies
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Comparative Thermal Analysis of Sleeve Connection Methods for Aluminum and Copper Conductors

Keon-Hee Park, Ye-Seul Seo, Jang-Seob Lim, Ga-Hyun Kim
The Transactions of The Korean Institute of Electrical Engineers
Electronic Packaging and Soldering Technologies
article

Comparative Thermal Analysis of Sleeve Connection Methods for Aluminum and Copper Conductors

Keon-Hee Park, Ye-Seul Seo, Jang-Seob Lim, Ga-Hyun Kim
article en

Abstract

Aluminum conductors are used in overhead transmission lines, while copper is used in underground and submarine cables. This study analyzed thermal characteristics of compression, bolted, and welded sleeves for aluminum, and compression and bolted sleeves for copper. Conductive compound and moisture compound removal effects on sleeve heating were evaluated under varying conditions. Thermal cycling tests per ANSI C119.4 and C119.0 standards (60-90℃) measured temperature differences between sleeves and reference conductors. Statistical analysis using Weibull and normal distributions showed bolted connection had best performance. Conductive compound applied with two outer moisture layers removed showed the lowest temperature. Similar patterns were observed at 600 A for aluminum and 900 A for copper, confirming aluminum's lower conductivity affects heating. Results provide baseline data for evaluating 70 kV aluminum underground and submarine cable joints..

The Transactions of The Korean Institute of Electrical EngineersVol. 75(3)
Openalex Percentile: Top 25%
Electronic Packaging and Soldering Technologies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.