A Lyapunov-Stable Direct Deadbeat Control Strategy for Grid-Current-Sensor-Only Active Power Filters

To improve the reliability and precision of shunt active power filters (APFs) under disturbances, this paper proposes an enhanced direct deadbeat control strategy requiring only grid-side current sensors. To this end, a sensor-lean yet robust framework is established by integrating PLL-less voltage estimation with online inductance identification. Specifically, the need for AC voltage sensors is eliminated by reconstructing the grid voltage from inverter outputs and consecutive current samples, while a load current feedforward mechanism further obviates the load current sensors. From an algorithmic perspective, the strategy utilizes the grid-side current as the direct controlled variable to minimize error propagation, while an online identification algorithm is incorporated to counteract parameter drift induced by magnetic saturation. Furthermore, system stability is rigorously guaranteed via Lyapunov theory. Validation through both simulation and experiments reveals that the grid current THD is reduced to 2.90% and 3.3%, respectively, with a dynamic response time within 20 ms. Ultimately, these findings confirm that the proposed scheme minimizes hardware dependency without compromising harmonic suppression or transient robustness.

Authors

Institutions

Publication Details

Journal
Electronics
Published
2026-03-04
DOI
https://doi.org/10.3390/electronics15051070
Primary Topic
Microgrid Control and Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

A Lyapunov-Stable Direct Deadbeat Control Strategy for Grid-Current-Sensor-Only Active Power Filters

Yankui Zhang, Jianling Liao
Electronics
Microgrid Control and Optimization
article

A Lyapunov-Stable Direct Deadbeat Control Strategy for Grid-Current-Sensor-Only Active Power Filters

Yankui Zhang, Jianling Liao
article en

Abstract

To improve the reliability and precision of shunt active power filters (APFs) under disturbances, this paper proposes an enhanced direct deadbeat control strategy requiring only grid-side current sensors. To this end, a sensor-lean yet robust framework is established by integrating PLL-less voltage estimation with online inductance identification. Specifically, the need for AC voltage sensors is eliminated by reconstructing the grid voltage from inverter outputs and consecutive current samples, while a load current feedforward mechanism further obviates the load current sensors. From an algorithmic perspective, the strategy utilizes the grid-side current as the direct controlled variable to minimize error propagation, while an online identification algorithm is incorporated to counteract parameter drift induced by magnetic saturation. Furthermore, system stability is rigorously guaranteed via Lyapunov theory. Validation through both simulation and experiments reveals that the grid current THD is reduced to 2.90% and 3.3%, respectively, with a dynamic response time within 20 ms. Ultimately, these findings confirm that the proposed scheme minimizes hardware dependency without compromising harmonic suppression or transient robustness.

ElectronicsVol. 15(5)
China University of Mining and Technology (CN)
Affordable and clean energy
Openalex Percentile: Top 36%
Microgrid Control and Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.