Failure of a Code-Compliant Reinforced Concrete Building: Damage Patterns and Nonlinear Seismic Response

This study investigates the seismic performance limitations of a newly constructed reinforced concrete building that collapsed during the 6 February 2023 Kahramanmaraş–Elbistan earthquake despite formal compliance with current seismic design requirements. Beyond the specific earthquake event, the study addresses a broader scientific problem: the limited understanding of the relationship between observed damage mechanisms and nonlinear dynamic response in mid-rise reinforced concrete buildings. The first part classifies recurring structural and non-structural damage patterns identified in newly constructed RC residences. The second part presents a nonlinear fiber-based static and dynamic analysis of a collapsed mid-rise building. Nonlinear dynamic analyses were conducted using ground motion records scaled to match the site-specific elastic design spectrum defined by TBDY 2018, corresponding to predefined seismic performance levels rather than an incremental dynamic analysis framework. The results indicate that an extremely low shear wall–to–floor area ratio (0.0357%) combined with asymmetric vertical element distribution significantly amplified torsional response and local shear demands. Nonlinear dynamic analyses showed that critical shear walls exceeded Collapse Prevention limits under DD2-level excitation, while system-level shear contribution limits remained within code-defined thresholds. Dynamic base shear demand corresponded to approximately 30% of the maximum nonlinear capacity obtained from pushover analysis, indicating that localized member failure rather than global strength deficiency governed the collapse mechanism. The analytically identified critical members were consistent with the observed collapse configuration, particularly at the soft ground story. The findings demonstrate that prescriptive code compliance alone may not ensure satisfactory seismic performance when structural irregularities, torsional amplification, and detailing deficiencies coexist. The results are consistent with damage patterns reported in other recent destructive earthquakes and contribute to improving the understanding of collapse mechanisms in code-compliant RC buildings.

Authors

Institutions

Publication Details

Journal
Buildings
Published
2026-03-04
DOI
https://doi.org/10.3390/buildings16051012
Citations
1
Primary Topic
Seismic Performance and Analysis
Type
article
Field-Weighted Citation Impact
19.37
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Failure of a Code-Compliant Reinforced Concrete Building: Damage Patterns and Nonlinear Seismic Response

İbrahim Baran Karaşin, Onur Onat, Burak Yön, Mehmet Emin Öncü et al.
1 citations
Buildings
Seismic Performance and Analysis
19.37
article

Failure of a Code-Compliant Reinforced Concrete Building: Damage Patterns and Nonlinear Seismic Response

İbrahim Baran Karaşin, Onur Onat, Burak Yön, Mehmet Emin Öncü, Ali Uslu, Sadık Varolgüneş
article en
1 citations

Abstract

This study investigates the seismic performance limitations of a newly constructed reinforced concrete building that collapsed during the 6 February 2023 Kahramanmaraş–Elbistan earthquake despite formal compliance with current seismic design requirements. Beyond the specific earthquake event, the study addresses a broader scientific problem: the limited understanding of the relationship between observed damage mechanisms and nonlinear dynamic response in mid-rise reinforced concrete buildings. The first part classifies recurring structural and non-structural damage patterns identified in newly constructed RC residences. The second part presents a nonlinear fiber-based static and dynamic analysis of a collapsed mid-rise building. Nonlinear dynamic analyses were conducted using ground motion records scaled to match the site-specific elastic design spectrum defined by TBDY 2018, corresponding to predefined seismic performance levels rather than an incremental dynamic analysis framework. The results indicate that an extremely low shear wall–to–floor area ratio (0.0357%) combined with asymmetric vertical element distribution significantly amplified torsional response and local shear demands. Nonlinear dynamic analyses showed that critical shear walls exceeded Collapse Prevention limits under DD2-level excitation, while system-level shear contribution limits remained within code-defined thresholds. Dynamic base shear demand corresponded to approximately 30% of the maximum nonlinear capacity obtained from pushover analysis, indicating that localized member failure rather than global strength deficiency governed the collapse mechanism. The analytically identified critical members were consistent with the observed collapse configuration, particularly at the soft ground story. The findings demonstrate that prescriptive code compliance alone may not ensure satisfactory seismic performance when structural irregularities, torsional amplification, and detailing deficiencies coexist. The results are consistent with damage patterns reported in other recent destructive earthquakes and contribute to improving the understanding of collapse mechanisms in code-compliant RC buildings.

BuildingsVol. 16(5)
Dicle University (TR), Bingöl University (TR), Inonu University (TR), Technical and Vocational University (IR), Munzur University (TR)
Sustainable cities and communities
Openalex Percentile: Top 1%
Seismic Performance and Analysis
19.37
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.