Experimental evaluation and accuracy analysis of inductive current transformers under realistic nonlinear and harmonic-rich load conditions

This paper provides an experimental evaluation of two current transformers' (CTs') accuracy performance under linear and nonlinear load scenarios. Four performance indicators-measured RMS current, total harmonic distortion (THD), ratio error, and phase error-were assessed across seven sample load scenarios in compliance with IEEE C57.13 and IEC 61,869 standards. The findings demonstrate that whereas CT accuracy is high under near-sinusoidal stimulation, it deteriorates with increasing waveform distortion and load current. Higher current levels exacerbate core nonlinearity and saturation, resulting in larger ratio and phase errors, while increased harmonic content increases THD and causes phase displacement between primary and secondary currents. In nonlinear circumstances, Actual current magnitudes are underestimated due to the constant attenuation of observed RMS values. This work's main contribution is a synchronized, time-domain experimental evaluation showing that phase error changes in tandem with ratio error and THD as functions of current magnitude and harmonic content. The limitations of sinusoidal-based CT accuracy classifications are revealed by this experimentally verified coupling between amplitude and angular inaccuracies. It also emphasizes the potential of sophisticated corrective techniques, such as real-time error detection, harmonic compensation, and artificial intelligence-based predictive modeling, to enhance CT reliability in distortion-rich power networks.

Authors

Institutions

Publication Details

Journal
Scientific Reports
Published
2026-03-03
DOI
https://doi.org/10.1038/s41598-026-41709-7
Primary Topic
Advanced Electrical Measurement Techniques
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Experimental evaluation and accuracy analysis of inductive current transformers under realistic nonlinear and harmonic-rich load conditions

Chouaib Labiod, Hassan Mana, Ali Bebboukha, Ievgen Zaitsev et al.
Scientific Reports
Advanced Electrical Measurement Techniques
article

Experimental evaluation and accuracy analysis of inductive current transformers under realistic nonlinear and harmonic-rich load conditions

Chouaib Labiod, Hassan Mana, Ali Bebboukha, Ievgen Zaitsev, Ben H. L. Daouli
article en

Abstract

This paper provides an experimental evaluation of two current transformers' (CTs') accuracy performance under linear and nonlinear load scenarios. Four performance indicators-measured RMS current, total harmonic distortion (THD), ratio error, and phase error-were assessed across seven sample load scenarios in compliance with IEEE C57.13 and IEC 61,869 standards. The findings demonstrate that whereas CT accuracy is high under near-sinusoidal stimulation, it deteriorates with increasing waveform distortion and load current. Higher current levels exacerbate core nonlinearity and saturation, resulting in larger ratio and phase errors, while increased harmonic content increases THD and causes phase displacement between primary and secondary currents. In nonlinear circumstances, Actual current magnitudes are underestimated due to the constant attenuation of observed RMS values. This work's main contribution is a synchronized, time-domain experimental evaluation showing that phase error changes in tandem with ratio error and THD as functions of current magnitude and harmonic content. The limitations of sinusoidal-based CT accuracy classifications are revealed by this experimentally verified coupling between amplitude and angular inaccuracies. It also emphasizes the potential of sophisticated corrective techniques, such as real-time error detection, harmonic compensation, and artificial intelligence-based predictive modeling, to enhance CT reliability in distortion-rich power networks.

Scientific ReportsVol. 16(1)
Taras Shevchenko National University of Kyiv (UA), University Ferhat Abbas of Setif (DZ), Institute of Electrodynamics (UA), Centre Hospitalo-Universitaire Bab El Oued (DZ)
Openalex Percentile: Top 39%
Advanced Electrical Measurement Techniques
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Experimental evaluation and accuracy analysis of inductive current transformers under realistic nonlinear and harmonic-rich load conditions — Chouaib Labiod, Hassan Mana, et al. · Scientific Reports (2026) | TGRS Research Map | TGRS