There are two factors that must be considered for the power quality analysis of an electrical power system, i.e. frequency and voltage stability. The system that can return to the initial condition or the steady state after a disturbance occurred indicates that the system is stable. This paper aims to detect the transient stability of three generators, which have identical specification of 2.25 MW 6.6 kV and are operated in parallel, based on the frequency performance. In this paper, the stability analysis is determined by using the nyquist method, where the system stability is indicated by the value of the response curve of the system. The analysis results show that the system of three paralleled generators have the value that far from 1 + j0 and the phase margin value and gain margin tend to be minimum. These values indicate that the system is unstable. The system slowly changes into more unstable because the oscillations are getting bigger until the final state. So, it is necessary to change the parameters of each generator that can affect the system stability during synchronization state.

Authors

Institutions

Publication Details

Journal
International Journal of Engineering & Technology
Published
2026-03-02
DOI
https://doi.org/10.14419/ijet.v7i4.36.28966
Primary Topic
Power System Optimization and Stability
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Analysis of Transient Stability in Synchronous Generator Using Nyquist Method

Syarifatul Izza, Mohammad Noor Hidayat, Ratna Ika Putri
International Journal of Engineering & Technology
Power System Optimization and Stability
article

Analysis of Transient Stability in Synchronous Generator Using Nyquist Method

Syarifatul Izza, Mohammad Noor Hidayat, Ratna Ika Putri
article en

Abstract

There are two factors that must be considered for the power quality analysis of an electrical power system, i.e. frequency and voltage stability. The system that can return to the initial condition or the steady state after a disturbance occurred indicates that the system is stable. This paper aims to detect the transient stability of three generators, which have identical specification of 2.25 MW 6.6 kV and are operated in parallel, based on the frequency performance. In this paper, the stability analysis is determined by using the nyquist method, where the system stability is indicated by the value of the response curve of the system. The analysis results show that the system of three paralleled generators have the value that far from 1 + j0 and the phase margin value and gain margin tend to be minimum. These values indicate that the system is unstable. The system slowly changes into more unstable because the oscillations are getting bigger until the final state. So, it is necessary to change the parameters of each generator that can affect the system stability during synchronization state.

International Journal of Engineering & TechnologyVol. 7(4.36)
State University of Malang (ID)
Affordable and clean energy
Openalex Percentile: Top 39%
Power System Optimization and Stability
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.