Experimental investigation on inclination effects during condensation heat transfer of R515B inside an inner-grooved tube

• Experimental analysis of condensation heat transfer in an inclined inner-grooved tube. • Effect of working conditions and tilting angle on heat transfer coefficient explained. • Marked effect of inclination angle at low mass velocity and low vapor quality. • Heat transfer coefficient showed a maximum value at −30° downward inclination. To address the gap existing in the open current literature regarding the effect of tilting angle during two-phase heat transfer inside inner-grooved tubes, this work investigates condensation heat transfer within a 7 mm OD inner-grooved tube. The refrigerant used is R515B, which is an azeotropic mixture selected for its favorable characteristics and low global warming potential. Experiments were performed at fixed saturation temperature of 30 °C, varying the mass flux in the range 50–400 kg/m²·s and the mean vapor quality from 0.06 to 0.93. The tube inclination relative to a horizontal plane was adjusted between -60° and +60°, in steps of 30°. Due to its significant effect on gravity-controlled condensation, the difference between the saturation and wall temperatures was kept constant throughout the tests, at selected values of 3 K and 6 K. Moreover, every test is accompanied with the corresponding flow pattern recorded with a high-speed camera to facilitate the understanding of the two-phase heat transfer mechanism. Findings revealed a noteworthy impact of inclination angle on the heat transfer coefficient. Overall, the most efficient thermal performance is achieved with a downward tube inclination of -30°, whereas the worst performance is observed with an upward inclination of +60°. These variations in performance are closely linked to variations in flow regimes and how gravity affects the thickness, distribution, and interfacial turbulence of the liquid film.

Authors

Institutions

Publication Details

Journal
International Journal of Heat and Mass Transfer
Published
2026-02-27
DOI
https://doi.org/10.1016/j.ijheatmasstransfer.2026.128586
Primary Topic
Heat Transfer and Boiling Studies
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Experimental investigation on inclination effects during condensation heat transfer of R515B inside an inner-grooved tube

Andrea Diani, Luisa Rossetto, Nima Irannezhad, Filippo Dalla Vecchia et al.
International Journal of Heat and Mass Transfer
Heat Transfer and Boiling Studies
article

Experimental investigation on inclination effects during condensation heat transfer of R515B inside an inner-grooved tube

Andrea Diani, Luisa Rossetto, Nima Irannezhad, Filippo Dalla Vecchia, Maryam Adwan
article en

Abstract

• Experimental analysis of condensation heat transfer in an inclined inner-grooved tube. • Effect of working conditions and tilting angle on heat transfer coefficient explained. • Marked effect of inclination angle at low mass velocity and low vapor quality. • Heat transfer coefficient showed a maximum value at −30° downward inclination. To address the gap existing in the open current literature regarding the effect of tilting angle during two-phase heat transfer inside inner-grooved tubes, this work investigates condensation heat transfer within a 7 mm OD inner-grooved tube. The refrigerant used is R515B, which is an azeotropic mixture selected for its favorable characteristics and low global warming potential. Experiments were performed at fixed saturation temperature of 30 °C, varying the mass flux in the range 50–400 kg/m²·s and the mean vapor quality from 0.06 to 0.93. The tube inclination relative to a horizontal plane was adjusted between -60° and +60°, in steps of 30°. Due to its significant effect on gravity-controlled condensation, the difference between the saturation and wall temperatures was kept constant throughout the tests, at selected values of 3 K and 6 K. Moreover, every test is accompanied with the corresponding flow pattern recorded with a high-speed camera to facilitate the understanding of the two-phase heat transfer mechanism. Findings revealed a noteworthy impact of inclination angle on the heat transfer coefficient. Overall, the most efficient thermal performance is achieved with a downward tube inclination of -30°, whereas the worst performance is observed with an upward inclination of +60°. These variations in performance are closely linked to variations in flow regimes and how gravity affects the thickness, distribution, and interfacial turbulence of the liquid film.

International Journal of Heat and Mass TransferVol. 261
University of Padua (IT), University of Maryland, College Park (US)
Affordable and clean energy
Openalex Percentile: Top 42%
Heat Transfer and Boiling Studies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.