An intelligent model and simulation of high voltage and medium voltage transmission line protection scheme using time overcurrent relay optimization settings: a case of Rwanda power network

This paper presents an optimized inverse-time overcurrent relay (OCR) setting and coordination methodology for interconnected high-voltage and medium-voltage (HV/MV) transmission systems, validated on a real 110 kV/15 kV utility substation network. Analytical feeder impedance equivalences and phase-to-phase fault current models were developed to evaluate relay performance under multiple fault locations ranging from 0% to 100% of feeder length. Standard inverse (SI), very inverse (VI), and extremely inverse (EI) IEC overcurrent relay characteristics were applied to both incoming and outgoing feeders. The study incorporates practical power system parameters, including short-circuit MVA, positive and negative sequence impedances, X/R ratio, transmission line length, current transformer (CT) ratios, full-load current, line capacity, grid frequency, and real power. Relay pickup currents and a fixed time multiplier setting (TMS = 0.05 s) were carefully selected to ensure safe, reliable, and rapid fault clearance. Fault current levels at each feeder location were computed based on feeder impedance variation, CT ratios, and pickup settings to determine optimal relay operating times and coordination intervals. Simulation results demonstrate that the proposed OCR coordination scheme achieves fast and selective fault isolation, with coordination interval times of 0.062–0.0927 s, 0.0720–0.0949 s, and 0.0661–0.0764 s for extremely inverse, very inverse, and standard inverse relay characteristics, respectively. The extremely inverse characteristic provided the fastest response for remote faults, while standard inverse relays ensured stable operation near the substation. MATLAB/Simulink-based validation confirms improved relay selectivity, reduced coordination delays, and effective mitigation of cascading outages. The results indicate that properly optimized inverse-time OCRs can provide a cost-effective, reliable, and practical protection solution for HV/MV transmission networks, particularly in developing and interconnected power grids where simplicity and coordination speed are critical.

Authors

Institutions

Publication Details

Journal
Discover Electronics
Published
2026-02-24
DOI
https://doi.org/10.1007/s44291-026-00173-3
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

An intelligent model and simulation of high voltage and medium voltage transmission line protection scheme using time overcurrent relay optimization settings: a case of Rwanda power network

Boniface Ntambara, Paul M. Wambua, Simiyu Sitati, Jean Bosco Byiringiro
Discover Electronics
Power Systems Fault Detection
article

An intelligent model and simulation of high voltage and medium voltage transmission line protection scheme using time overcurrent relay optimization settings: a case of Rwanda power network

Boniface Ntambara, Paul M. Wambua, Simiyu Sitati, Jean Bosco Byiringiro
article en

Abstract

This paper presents an optimized inverse-time overcurrent relay (OCR) setting and coordination methodology for interconnected high-voltage and medium-voltage (HV/MV) transmission systems, validated on a real 110 kV/15 kV utility substation network. Analytical feeder impedance equivalences and phase-to-phase fault current models were developed to evaluate relay performance under multiple fault locations ranging from 0% to 100% of feeder length. Standard inverse (SI), very inverse (VI), and extremely inverse (EI) IEC overcurrent relay characteristics were applied to both incoming and outgoing feeders. The study incorporates practical power system parameters, including short-circuit MVA, positive and negative sequence impedances, X/R ratio, transmission line length, current transformer (CT) ratios, full-load current, line capacity, grid frequency, and real power. Relay pickup currents and a fixed time multiplier setting (TMS = 0.05 s) were carefully selected to ensure safe, reliable, and rapid fault clearance. Fault current levels at each feeder location were computed based on feeder impedance variation, CT ratios, and pickup settings to determine optimal relay operating times and coordination intervals. Simulation results demonstrate that the proposed OCR coordination scheme achieves fast and selective fault isolation, with coordination interval times of 0.062–0.0927 s, 0.0720–0.0949 s, and 0.0661–0.0764 s for extremely inverse, very inverse, and standard inverse relay characteristics, respectively. The extremely inverse characteristic provided the fastest response for remote faults, while standard inverse relays ensured stable operation near the substation. MATLAB/Simulink-based validation confirms improved relay selectivity, reduced coordination delays, and effective mitigation of cascading outages. The results indicate that properly optimized inverse-time OCRs can provide a cost-effective, reliable, and practical protection solution for HV/MV transmission networks, particularly in developing and interconnected power grids where simplicity and coordination speed are critical.

Discover ElectronicsVol. 3(1)
Technical University of Kenya (KE), Moi University (KE), Dedan Kimathi University of Technology (KE), Rwanda Development Board (RW)
Affordable and clean energy
Openalex Percentile: Top 47%
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.