Improving Flow Efficiency via Internal Flow Channel Optimization Design in a Novel Non-Pressurized Diaphragm Deluge Alarm Valve
Automatic sprinkler systems are widely used for fire protection in various buildings, with deluge valves serving as the core component of these systems. Traditional deluge valves employ a diaphragm-type design (Zoning Sprinkler Fire Monitor, ZSFM), which is prone to significant safety hazards such as corrosion and damage due to uneven pressure distribution on the diaphragm. This study modified a 150 mm diameter ZSFM to a non-pressure diaphragm type, establishing and validating a CFD model of the internal flow field. Based on the original structure, six drag reduction optimization cases are designed. Among these, case 5 exhibits the minimum inlet-to-outlet pressure drop of 0.050 MPa under rated operating conditions, meeting and significantly exceeding the fire protection industry standard (≤0.08 MPa).
Authors
- Zongheng Chen
- Jieqing Zheng
- Tianyi Zheng
- Jinhao Zhang
- Yan Zheng
- Zijie Yin
- Jun Wang
Institutions
- Jimei University (CN)
- Institute of Navigation (US)
Publication Details
- Journal
- Applied Sciences
- Published
- 2026-02-21
- DOI
- https://doi.org/10.3390/app16042111
- Primary Topic
- Fire dynamics and safety research
- Type
- article
- Field-Weighted Citation Impact
- 0.00
Funders
- Natural Science Foundation of Fujian Province
- Jimei University