This study presents a systematic investigation into the seismic performance of precast concrete shear walls using cold-extruded sleeve connections for reinforcement splicing. Quasi-static cyclic loading tests were conducted on a full-scale precast wall specimen and a cast-in-place reference wall to evaluate the influence of construction joint detailing on structural behavior. The experimental results show that the precast wall exhibited progressive crack propagation, stable energy dissipation, and slightly higher ultimate lateral load and deformation capacity compared to the cast-in-place counterpart. In contrast, the cast-in-place wall experienced abrupt failure due to concrete spalling and out-of-plane splitting, highlighting the critical importance of reinforcement continuity and joint configuration. To further investigate key design parameters, high-fidelity finite element models were developed in ABAQUS. Concrete was modeled using the Concrete Damaged Plasticity model, while steel rebars and sleeves were simulated with a bilinear constitutive law. The numerical simulations, validated against experimental data, achieved good agreement in terms of load-drift response, crack patterns, and stress distributions. A parametric study was conducted by varying the wall aspect ratio, axial compression ratio, and longitudinal reinforcement ratio in the boundary elements. The results indicate that both the aspect ratio and axial compression ratio have significant effects on lateral load capacity and drift capacity, whereas the reinforcement ratio in the boundary elements exerts a relatively minor influence. For walls with low shear-span-to-depth ratios and high axial compression, increasing both longitudinal and horizontal reinforcement leads to noticeable improvements in load-carrying capacity and ductility. These findings confirm the reliability of the cold-extruded sleeve connection system in precast shear wall applications. The study establishes a validated numerical framework for seismic performance prediction and provides practical guidance for optimizing the design of prefabricated walls. This contributes to enhancing structural safety and improving seismic ductility, thereby supporting the broader adoption of precast systems in sustainable construction.

Authors

Institutions

Publication Details

Journal
Buildings
Published
2026-02-21
DOI
https://doi.org/10.3390/buildings16040866
Primary Topic
Seismic Performance and Analysis
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Analysis of the Effect of Cold-Extruded Sleeve Connection on the Stability of Prefabricated Shear Walls

Yingrui Chen, Guang-Bin Pan, Jian Cai
Buildings
Seismic Performance and Analysis
article

Analysis of the Effect of Cold-Extruded Sleeve Connection on the Stability of Prefabricated Shear Walls

Yingrui Chen, Guang-Bin Pan, Jian Cai
article en

Abstract

This study presents a systematic investigation into the seismic performance of precast concrete shear walls using cold-extruded sleeve connections for reinforcement splicing. Quasi-static cyclic loading tests were conducted on a full-scale precast wall specimen and a cast-in-place reference wall to evaluate the influence of construction joint detailing on structural behavior. The experimental results show that the precast wall exhibited progressive crack propagation, stable energy dissipation, and slightly higher ultimate lateral load and deformation capacity compared to the cast-in-place counterpart. In contrast, the cast-in-place wall experienced abrupt failure due to concrete spalling and out-of-plane splitting, highlighting the critical importance of reinforcement continuity and joint configuration. To further investigate key design parameters, high-fidelity finite element models were developed in ABAQUS. Concrete was modeled using the Concrete Damaged Plasticity model, while steel rebars and sleeves were simulated with a bilinear constitutive law. The numerical simulations, validated against experimental data, achieved good agreement in terms of load-drift response, crack patterns, and stress distributions. A parametric study was conducted by varying the wall aspect ratio, axial compression ratio, and longitudinal reinforcement ratio in the boundary elements. The results indicate that both the aspect ratio and axial compression ratio have significant effects on lateral load capacity and drift capacity, whereas the reinforcement ratio in the boundary elements exerts a relatively minor influence. For walls with low shear-span-to-depth ratios and high axial compression, increasing both longitudinal and horizontal reinforcement leads to noticeable improvements in load-carrying capacity and ductility. These findings confirm the reliability of the cold-extruded sleeve connection system in precast shear wall applications. The study establishes a validated numerical framework for seismic performance prediction and provides practical guidance for optimizing the design of prefabricated walls. This contributes to enhancing structural safety and improving seismic ductility, thereby supporting the broader adoption of precast systems in sustainable construction.

BuildingsVol. 16(4)
Guangzhou Panyu Polytechnic (CN), Guangdong Polytechnic Normal University (CN), South China University of Technology (CN)
Openalex Percentile: Top 48%
Seismic Performance and Analysis
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.