Physical Simulation of Two-Phase and Two-Phase Zero-Conductor Short Circuits in a Rural 0.4-kV Power-Supply Network

Rural power supply networks feature two-phase and two-phase zero-conductor short-circuits in the case of crossed uninsulated wires or damaged insulated wires. It is practically impossible to detect the parameters of these modes, so they should be calculated. However, normative documents and literature sources do not provide dependencies to identify these modes along the entire length of the transmission line, including at the point of installation of sectionalizing devices. In order to determine the electrical parameters characteristic for the modes of two-phase and two-phase zero-conductor short circuits in rural 0.4-kV power supply networks, the authors used the method of physical simulation. The physical model of a rural power supply network contained a TT-0.16-380/38 Y/Yn-0 transformer. The phase-to-phase voltage ratio was 38/22 V. The authors used a nichrome wire of X20H80 alloy with a cross section of 0.5 mm2 and a resistance of 5.6 Ω/m. The transformer neutral grounding resistance was taken as 4 Ω, and that of 30 Ω was taken for two repeated neutral wire grounding. As a result, it was found that, in a two-phase short circuit in a 0.4-kV network, the currents in the damaged phases are equal and the ratio of voltages on the undamaged and damaged phases was 1.3–1.9. In the case of a two-phase short circuit to the neutral conductor in one of the phases, the current value is equal to the algebraic sum of the neutral current and the current flowing in the other phase. At the same time, the voltage ratio of the undamaged phase to the damaged phases changes depending on the proximity to the fault point. The revealed dependences can be used to identify these modes by microcontroller control units of sectionalizing devices, which will provide the network dispatcher with information about their occurrence and reduce the time for search and identification of the causes of damage.

Authors

Institutions

Publication Details

Journal
Technical Physics Letters
Published
2025-09-01
DOI
https://doi.org/10.1134/s1063785025700361
Primary Topic
Electric Power Systems and Control
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Physical Simulation of Two-Phase and Two-Phase Zero-Conductor Short Circuits in a Rural 0.4-kV Power-Supply Network

A. A. Lansberg, A. V. Vinogradov
Technical Physics Letters
Electric Power Systems and Control
article

Physical Simulation of Two-Phase and Two-Phase Zero-Conductor Short Circuits in a Rural 0.4-kV Power-Supply Network

A. A. Lansberg, A. V. Vinogradov
article en

Abstract

Rural power supply networks feature two-phase and two-phase zero-conductor short-circuits in the case of crossed uninsulated wires or damaged insulated wires. It is practically impossible to detect the parameters of these modes, so they should be calculated. However, normative documents and literature sources do not provide dependencies to identify these modes along the entire length of the transmission line, including at the point of installation of sectionalizing devices. In order to determine the electrical parameters characteristic for the modes of two-phase and two-phase zero-conductor short circuits in rural 0.4-kV power supply networks, the authors used the method of physical simulation. The physical model of a rural power supply network contained a TT-0.16-380/38 Y/Yn-0 transformer. The phase-to-phase voltage ratio was 38/22 V. The authors used a nichrome wire of X20H80 alloy with a cross section of 0.5 mm2 and a resistance of 5.6 Ω/m. The transformer neutral grounding resistance was taken as 4 Ω, and that of 30 Ω was taken for two repeated neutral wire grounding. As a result, it was found that, in a two-phase short circuit in a 0.4-kV network, the currents in the damaged phases are equal and the ratio of voltages on the undamaged and damaged phases was 1.3–1.9. In the case of a two-phase short circuit to the neutral conductor in one of the phases, the current value is equal to the algebraic sum of the neutral current and the current flowing in the other phase. At the same time, the voltage ratio of the undamaged phase to the damaged phases changes depending on the proximity to the fault point. The revealed dependences can be used to identify these modes by microcontroller control units of sectionalizing devices, which will provide the network dispatcher with information about their occurrence and reduce the time for search and identification of the causes of damage.

Technical Physics LettersVol. 51(9)
Federal Scientific Agroengineering Center VIM (RU)
Openalex Percentile: Top 35%
Electric Power Systems and Control
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Physical Simulation of Two-Phase and Two-Phase Zero-Conductor Short Circuits in a Rural 0.4-kV Power-Supply Network — A. A. Lansberg, A. V. Vinogradov · Technical Physics Letters (2025) | TGRS Research Map | TGRS