Ground fault identification method for LVDC distribution networks based on active signal injection and phase feature analysis

To accurately and reliably identify ground faults in low-voltage DC (LVDC) distribution networks and address the limitations of existing transient-based methods in terms of sensitivity and reliability, this paper proposes a ground fault identification method based on active signal injection. By introducing an auxiliary control strategy in the voltage source converter (VSC), a specific-frequency probing signal is actively injected after protection is triggered to enhance fault characteristics. Zero-sequence currents from each feeder are then compared with the system's total zero-sequence current using cross-correlation to determine the optimal alignment delay. At this delay point, the phase difference cosine is calculated and used as the fault identification criterion. Simulation results confirm that the proposed method is highly reliable and effective.

Authors

Institutions

Publication Details

Journal
IET conference proceedings.
Published
2026-02-19
DOI
https://doi.org/10.1049/icp.2025.3966
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Ground fault identification method for LVDC distribution networks based on active signal injection and phase feature analysis

Yanqun Liao, Jin Li, Jianan Ye, Yong Chen et al.
IET conference proceedings.
HVDC Systems and Fault Protection
article

Ground fault identification method for LVDC distribution networks based on active signal injection and phase feature analysis

Yanqun Liao, Jin Li, Jianan Ye, Yong Chen, Jiayi Yang
article en

Abstract

To accurately and reliably identify ground faults in low-voltage DC (LVDC) distribution networks and address the limitations of existing transient-based methods in terms of sensitivity and reliability, this paper proposes a ground fault identification method based on active signal injection. By introducing an auxiliary control strategy in the voltage source converter (VSC), a specific-frequency probing signal is actively injected after protection is triggered to enhance fault characteristics. Zero-sequence currents from each feeder are then compared with the system's total zero-sequence current using cross-correlation to determine the optimal alignment delay. At this delay point, the phase difference cosine is calculated and used as the fault identification criterion. Simulation results confirm that the proposed method is highly reliable and effective.

IET conference proceedings.Vol. 2025(38)
China Southern Power Grid (China) (CN)
Openalex Percentile: Top 51%
HVDC Systems and Fault Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.