Method of power differential protection for distribution network containing inverter-interfaced distributed generator

• A positive-sequence power fault component differential protection method is proposed. • A weighted power vector is proposed, and a power differential criterion is formulated based on the phase difference between the weighted power factors of the power fault components at both ends. • Resolves the near-end fault blind zone (reduced to 5% of the line length) and maloperation under high DG penetration levels (up to 90%). • Simulations confirm robust performance under 5dB SNR measurement noise, transition resistances up to 300Ω, while remaining unaffected by CT saturation. The increasing penetration of inverter-interfaced distributed generators (DGs) has significantly altered the structure, power flow patterns, and operating modes of modern distribution networks. These changes have degraded the dependability of conventional single-ended protection schemes. To address this issue, this study proposes a power differential protection method. First, by considering the output characteristics of distributed generators with low-voltage ride-through (LVRT) controlling strategies, the magnitude and directional characteristics of the positive-sequence differential power components at both ends of the distribution line are examined. Next, a weighted power vector is introduced, and based on its phase difference with the power fault components at both ends, a power differential criterion is developed to resolve the difficulty of distinguishing between normal unbalanced current and fault current caused by DG branches. Finally, simulation results demonstrate that the method maintains reliable performance under a range of challenging conditions, including near‑end faults as close as 5% of the line length, transition resistances up to 300 Ω, current transformer (CT) saturation, DG penetration levels up to 90%, load variations, control strategies, measurement noise with an SNR of 5 dB and time desynchronization up to 20 ms.

Authors

Institutions

Publication Details

Journal
Electric Power Systems Research
Published
2026-02-19
DOI
https://doi.org/10.1016/j.epsr.2026.112825
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Method of power differential protection for distribution network containing inverter-interfaced distributed generator

Guomin Luo, Hailong Zhang, Yingjie Tan, Mengyu Wu et al.
Electric Power Systems Research
Power Systems Fault Detection
article

Method of power differential protection for distribution network containing inverter-interfaced distributed generator

Guomin Luo, Hailong Zhang, Yingjie Tan, Mengyu Wu, Jinghan He, Guoliang Lv, Yapeng Wang
article en

Abstract

• A positive-sequence power fault component differential protection method is proposed. • A weighted power vector is proposed, and a power differential criterion is formulated based on the phase difference between the weighted power factors of the power fault components at both ends. • Resolves the near-end fault blind zone (reduced to 5% of the line length) and maloperation under high DG penetration levels (up to 90%). • Simulations confirm robust performance under 5dB SNR measurement noise, transition resistances up to 300Ω, while remaining unaffected by CT saturation. The increasing penetration of inverter-interfaced distributed generators (DGs) has significantly altered the structure, power flow patterns, and operating modes of modern distribution networks. These changes have degraded the dependability of conventional single-ended protection schemes. To address this issue, this study proposes a power differential protection method. First, by considering the output characteristics of distributed generators with low-voltage ride-through (LVRT) controlling strategies, the magnitude and directional characteristics of the positive-sequence differential power components at both ends of the distribution line are examined. Next, a weighted power vector is introduced, and based on its phase difference with the power fault components at both ends, a power differential criterion is developed to resolve the difficulty of distinguishing between normal unbalanced current and fault current caused by DG branches. Finally, simulation results demonstrate that the method maintains reliable performance under a range of challenging conditions, including near‑end faults as close as 5% of the line length, transition resistances up to 300 Ω, current transformer (CT) saturation, DG penetration levels up to 90%, load variations, control strategies, measurement noise with an SNR of 5 dB and time desynchronization up to 20 ms.

Electric Power Systems ResearchVol. 256
State Grid Corporation of China (China) (CN), Beijing Jiaotong University (CN)
Affordable and clean energy
Openalex Percentile: Top 51%
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.