Thermal calculation of the heating block of a high-pressure direct contact heater based on an experimental study
The accurate study of heat transfer between water and steam at high pressures was achieved on a developed and tested model of a mixing unit for heat transfer flows (Direct-Contact Water Heater — DCWH). The test results showed that the water underheating to the saturation temperature at the model outlet is less than 1 and 2°C for two- and single-tray arrangement of the water-separation unit in the model, respectively. The droplet flow model is preferable for thermal calculation of the heating block in the DCWH.
Authors
- Yu. G. Sukhorukov
- P. V. Egorov
- B. F. Balunov
- V. D. Lychakov
- Yu. V. Usov
- F. A. Svyatkin
- A. S. Matyash
Institutions
- Peter the Great St. Petersburg Polytechnic University (RU)
- Russian Scientific Center "Applied Chemistry" (RU)
Publication Details
- Journal
- Thermophysics and Aeromechanics
- Published
- 2026-02-13
- DOI
- https://doi.org/10.1134/s0869864325020088
- Primary Topic
- Refrigeration and Air Conditioning Technologies
- Type
- article
- Field-Weighted Citation Impact
- 0.00