Experimental study on airflow-induced particle resuspension from carpet under floor-supply displacement ventilation
• Particle resuspension on carpet was tested under floor-supply displacement ventilation. • Resuspension rate ranged 10⁻⁸–10⁻⁴ h⁻¹ depending on supply velocity and humidity. • Larger particles (>10 μm) showed greater resuspension under upward airflow. • Under CCD, resuspension was 10⁻⁵–10⁻³ h⁻¹ for 0.3–3 μm, nearly zero for ≥10 μm. • FSDV airflow caused no excessive resuspension compared with walking-induced cases. . Application of floor-supply displacement ventilation (FSDV) in medical facilities remains limited due to concerns about particle resuspension, including infectious droplets and dust from shoes. However, research data on this phenomenon under FSDV airflow are scarce. This study aimed to quantitatively evaluate particle resuspension under FSDV conditions and compare it with a circular ceiling diffuser (CCD) system. Experiments were conducted in a cleanroom chamber. For FSDV, the floor supply velocity (vf = 0.040, 0.030, and 0.010 m/s) and relative humidity (20%, 50%, and 80%) were varied. For CCD, the airflow rate (850, 750, and 250 m³/h) was varied at 50% relative humidity. Particle concentrations were measured using particle counters to calculate resuspension rates. Microscopic observations of carpet fibers above perforations were also performed to assess microscale resuspension behavior. Both supply velocity and humidity significantly affected resuspension under FSDV. The resuspension rate ranged from 10⁻⁷–10⁻⁴ h⁻¹ ( v f = 0.040 m/s, 50 ACH) and 10⁻⁸–10⁻⁵ h⁻¹ ( v f = 0.010 m/s, 12 ACH), showing that higher velocity and lower humidity enhanced resuspension. The resuspension rate increased with particle size, and large agglomerates (>10 μm) observed microscopically were more likely to detach due to greater exposed surface area to upward airflow. Under CCD, rates ranged from 10⁻⁵–10⁻³ h⁻¹ for 0.3–3 μm particles but were near zero for ≥10 μm. Airflow-induced resuspension under FSDV was smaller than that reported for walking-induced resuspension, even under high air exchange rates. This indicates that FSDV does not inherently increase resuspension risk under the tested conditions.
Authors
- Hisako Nagata
- Toshio Yamanaka
- Jun Yoshihara (ORCID: https://orcid.org/0009-0005-8013-8038)
- Haruna Yamasawa (ORCID: https://orcid.org/0000-0002-1262-8781)
- Shigeru Okamoto (ORCID: https://orcid.org/0000-0002-8773-5194)
- Tomohiro Kobayashi (ORCID: https://orcid.org/0000-0003-4956-1274)
- Noriaki Kobayashi
Institutions
- Kubota (Japan) (JP)
- The University of Osaka (JP)
Publication Details
- Journal
- Building and Environment
- Published
- 2026-02-13
- DOI
- https://doi.org/10.1016/j.buildenv.2026.114360
- Primary Topic
- Infection Control and Ventilation
- Type
- article
- Field-Weighted Citation Impact
- 0.00