Experimental study on airflow-induced particle resuspension from carpet under floor-supply displacement ventilation

• Particle resuspension on carpet was tested under floor-supply displacement ventilation. • Resuspension rate ranged 10⁻⁸–10⁻⁴ h⁻¹ depending on supply velocity and humidity. • Larger particles (>10 μm) showed greater resuspension under upward airflow. • Under CCD, resuspension was 10⁻⁵–10⁻³ h⁻¹ for 0.3–3 μm, nearly zero for ≥10 μm. • FSDV airflow caused no excessive resuspension compared with walking-induced cases. . Application of floor-supply displacement ventilation (FSDV) in medical facilities remains limited due to concerns about particle resuspension, including infectious droplets and dust from shoes. However, research data on this phenomenon under FSDV airflow are scarce. This study aimed to quantitatively evaluate particle resuspension under FSDV conditions and compare it with a circular ceiling diffuser (CCD) system. Experiments were conducted in a cleanroom chamber. For FSDV, the floor supply velocity (vf = 0.040, 0.030, and 0.010 m/s) and relative humidity (20%, 50%, and 80%) were varied. For CCD, the airflow rate (850, 750, and 250 m³/h) was varied at 50% relative humidity. Particle concentrations were measured using particle counters to calculate resuspension rates. Microscopic observations of carpet fibers above perforations were also performed to assess microscale resuspension behavior. Both supply velocity and humidity significantly affected resuspension under FSDV. The resuspension rate ranged from 10⁻⁷–10⁻⁴ h⁻¹ ( v f = 0.040 m/s, 50 ACH) and 10⁻⁸–10⁻⁵ h⁻¹ ( v f = 0.010 m/s, 12 ACH), showing that higher velocity and lower humidity enhanced resuspension. The resuspension rate increased with particle size, and large agglomerates (>10 μm) observed microscopically were more likely to detach due to greater exposed surface area to upward airflow. Under CCD, rates ranged from 10⁻⁵–10⁻³ h⁻¹ for 0.3–3 μm particles but were near zero for ≥10 μm. Airflow-induced resuspension under FSDV was smaller than that reported for walking-induced resuspension, even under high air exchange rates. This indicates that FSDV does not inherently increase resuspension risk under the tested conditions.

Authors

Institutions

Publication Details

Journal
Building and Environment
Published
2026-02-13
DOI
https://doi.org/10.1016/j.buildenv.2026.114360
Primary Topic
Infection Control and Ventilation
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Experimental study on airflow-induced particle resuspension from carpet under floor-supply displacement ventilation

Hisako Nagata, Toshio Yamanaka, Jun Yoshihara, Haruna Yamasawa et al.
Building and Environment
Infection Control and Ventilation
article

Experimental study on airflow-induced particle resuspension from carpet under floor-supply displacement ventilation

Hisako Nagata, Toshio Yamanaka, Jun Yoshihara, Haruna Yamasawa, Shigeru Okamoto, Tomohiro Kobayashi, Noriaki Kobayashi
article en

Abstract

• Particle resuspension on carpet was tested under floor-supply displacement ventilation. • Resuspension rate ranged 10⁻⁸–10⁻⁴ h⁻¹ depending on supply velocity and humidity. • Larger particles (>10 μm) showed greater resuspension under upward airflow. • Under CCD, resuspension was 10⁻⁵–10⁻³ h⁻¹ for 0.3–3 μm, nearly zero for ≥10 μm. • FSDV airflow caused no excessive resuspension compared with walking-induced cases. . Application of floor-supply displacement ventilation (FSDV) in medical facilities remains limited due to concerns about particle resuspension, including infectious droplets and dust from shoes. However, research data on this phenomenon under FSDV airflow are scarce. This study aimed to quantitatively evaluate particle resuspension under FSDV conditions and compare it with a circular ceiling diffuser (CCD) system. Experiments were conducted in a cleanroom chamber. For FSDV, the floor supply velocity (vf = 0.040, 0.030, and 0.010 m/s) and relative humidity (20%, 50%, and 80%) were varied. For CCD, the airflow rate (850, 750, and 250 m³/h) was varied at 50% relative humidity. Particle concentrations were measured using particle counters to calculate resuspension rates. Microscopic observations of carpet fibers above perforations were also performed to assess microscale resuspension behavior. Both supply velocity and humidity significantly affected resuspension under FSDV. The resuspension rate ranged from 10⁻⁷–10⁻⁴ h⁻¹ ( v f = 0.040 m/s, 50 ACH) and 10⁻⁸–10⁻⁵ h⁻¹ ( v f = 0.010 m/s, 12 ACH), showing that higher velocity and lower humidity enhanced resuspension. The resuspension rate increased with particle size, and large agglomerates (>10 μm) observed microscopically were more likely to detach due to greater exposed surface area to upward airflow. Under CCD, rates ranged from 10⁻⁵–10⁻³ h⁻¹ for 0.3–3 μm particles but were near zero for ≥10 μm. Airflow-induced resuspension under FSDV was smaller than that reported for walking-induced resuspension, even under high air exchange rates. This indicates that FSDV does not inherently increase resuspension risk under the tested conditions.

Building and EnvironmentVol. 294
Kubota (Japan) (JP), The University of Osaka (JP)
Openalex Percentile: Top 58%
Infection Control and Ventilation
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.