A Novel Ground Distance Protection Algorithm for Non-Uniform Power Transmission Lines

In this paper, the performance of a conventional distance protection relay employing a single ground compensation factor (k0) per protection zone is investigated for non-uniform transmission lines consisting of mixed overhead line and underground cable sections. In such composite lines, the use of a single k0 value may lead to inaccurate apparent impedance calculation during phase-to-ground faults due to significant differences in zero- and positive-sequence parameters among line sections. To address this limitation, a novel ground distance protection algorithm is proposed, which applies separate ground compensation factors corresponding to individual line sections within the same distance protection zone. The proposed algorithm dynamically identifies the faulted line section based on the measured reactance and selects the appropriate compensation factor accordingly. A three-section composite transmission line model is developed in the ATP–EMTP environment, including overhead and cable segments with different electrical characteristics. Phase-to-ground faults are simulated at various locations along each line section, and the apparent impedances calculated using the proposed algorithm are quantitatively compared with those obtained from the classical ground distance protection algorithm. Simulation results demonstrate that, under resistive fault conditions (Rarc = 1 Ω), the proposed method reduces impedance magnitude estimation errors from over 23% to below 7%, while maintaining comparable or improved angle estimation accuracy across the protected zone. Although the proposed algorithm introduces an additional computational step due to the selection of appropriate ground compensation factors for individual line sections, this aspect has not been evaluated under real-time conditions and is left for future implementation-oriented studies. Overall, the proposed approach offers a practical and effective solution for improving ground distance protection performance in non-uniform transmission lines.

Authors

Institutions

Publication Details

Journal
Energies
Published
2026-02-12
DOI
https://doi.org/10.3390/en19040966
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

A Novel Ground Distance Protection Algorithm for Non-Uniform Power Transmission Lines

Mehmet Bayrak, Ali Toruş
Energies
Power Systems Fault Detection
article

A Novel Ground Distance Protection Algorithm for Non-Uniform Power Transmission Lines

Mehmet Bayrak, Ali Toruş
article en

Abstract

In this paper, the performance of a conventional distance protection relay employing a single ground compensation factor (k0) per protection zone is investigated for non-uniform transmission lines consisting of mixed overhead line and underground cable sections. In such composite lines, the use of a single k0 value may lead to inaccurate apparent impedance calculation during phase-to-ground faults due to significant differences in zero- and positive-sequence parameters among line sections. To address this limitation, a novel ground distance protection algorithm is proposed, which applies separate ground compensation factors corresponding to individual line sections within the same distance protection zone. The proposed algorithm dynamically identifies the faulted line section based on the measured reactance and selects the appropriate compensation factor accordingly. A three-section composite transmission line model is developed in the ATP–EMTP environment, including overhead and cable segments with different electrical characteristics. Phase-to-ground faults are simulated at various locations along each line section, and the apparent impedances calculated using the proposed algorithm are quantitatively compared with those obtained from the classical ground distance protection algorithm. Simulation results demonstrate that, under resistive fault conditions (Rarc = 1 Ω), the proposed method reduces impedance magnitude estimation errors from over 23% to below 7%, while maintaining comparable or improved angle estimation accuracy across the protected zone. Although the proposed algorithm introduces an additional computational step due to the selection of appropriate ground compensation factors for individual line sections, this aspect has not been evaluated under real-time conditions and is left for future implementation-oriented studies. Overall, the proposed approach offers a practical and effective solution for improving ground distance protection performance in non-uniform transmission lines.

EnergiesVol. 19(4)
Sakarya University (TR)
Openalex Percentile: Top 59%
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.