Research on the characteristic parameter analysis and monitoring method of dry-type reactor turn-to-turn insulation degradation

One of the main causes of dry-type reactor failures is turn-to-turn short-circuit faults, where the operational safety of the equipment is greatly influenced by the condition of the turn-to-turn insulation. We thoroughly examine the evolutionary trends of important parameters such as winding current, short-circuit ring current and voltage, equivalent impedance, and winding phase angle during the insulation deterioration process using simulated turn-to-turn insulation degradation. We find winding current and equivalent impedance change is less than 15 % when insulation deteriorates; short-circuit ring current changes significantly but is hard to observe in practice; phase angle changes sharply and readily; the critical resistance thresholds for insulation degradation and total failure are determined to be 1000mΩ and 10mΩ, respectively; the phase angle change rate (x) is a useful indicator: x < 20 % denotes normal insulation, 20 %≤x < 100 % indicates continuous degradation, and x ≥ 100 % indicates insulation failure. Leveraging these findings, a novel monitoring method utilizing the winding phase angle change rate was proposed, and its feasibility was experimentally validated. Compared with conventional approaches, the proposed method demonstrates a 300 % sensitivity enhancement.

Authors

Publication Details

Journal
Results in Engineering
Published
2026-02-04
DOI
https://doi.org/10.1016/j.rineng.2026.109449
Primary Topic
Reliability and Maintenance Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Research on the characteristic parameter analysis and monitoring method of dry-type reactor turn-to-turn insulation degradation

Jiafei Liu, Zhiyun Xu Lin Han, Wenqi Wang, Liang Zou et al.
Results in Engineering
Reliability and Maintenance Optimization
article

Research on the characteristic parameter analysis and monitoring method of dry-type reactor turn-to-turn insulation degradation

Jiafei Liu, Zhiyun Xu Lin Han, Wenqi Wang, Liang Zou, Kun Guo
article en

Abstract

One of the main causes of dry-type reactor failures is turn-to-turn short-circuit faults, where the operational safety of the equipment is greatly influenced by the condition of the turn-to-turn insulation. We thoroughly examine the evolutionary trends of important parameters such as winding current, short-circuit ring current and voltage, equivalent impedance, and winding phase angle during the insulation deterioration process using simulated turn-to-turn insulation degradation. We find winding current and equivalent impedance change is less than 15 % when insulation deteriorates; short-circuit ring current changes significantly but is hard to observe in practice; phase angle changes sharply and readily; the critical resistance thresholds for insulation degradation and total failure are determined to be 1000mΩ and 10mΩ, respectively; the phase angle change rate (x) is a useful indicator: x < 20 % denotes normal insulation, 20 %≤x < 100 % indicates continuous degradation, and x ≥ 100 % indicates insulation failure. Leveraging these findings, a novel monitoring method utilizing the winding phase angle change rate was proposed, and its feasibility was experimentally validated. Compared with conventional approaches, the proposed method demonstrates a 300 % sensitivity enhancement.

Results in EngineeringVol. 29
Openalex Percentile: Top 73%
Reliability and Maintenance Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Research on the characteristic parameter analysis and monitoring method of dry-type reactor turn-to-turn insulation degradation — Jiafei Liu, Zhiyun Xu Lin Han, et al. · Results in Engineering (2026) | TGRS Research Map | TGRS