Application of artificial intelligence for optimal control of reactive power compensation in AC traction power supply systems

The study aimed to quantitatively assess the effectiveness of neural network-based control of dynamic reactive power compensation in the traction network of Ukrzaliznytsia. The methodology involved high-frequency monitoring of 118 substations (≈16 trillion measurements), aggregation of 52 million Supervisory Control and Data Acquisition records, Theil-Sen trend estimation, Seasonal-Trend decomposition using Loess, the Brown Forsythe test, and a deep neural network with 64-32-16 layers optimised through a Tree-structured Parzen Estimator, validated in 120 Monte Carlo scenarios in Simscape. The results demonstrated that the average daily Q increased from 309.8 to 367.2 Mvar (18.5%) with a trend of 0.95 Mvar/month (95% CI 0.82-1.08; p < 0.001). Winter peaks reached 520 Mvar, while variance after February 2022 increased 1.5-fold (F = 34.9; p < 0.001). The neural network achieved Mean Squared Error = 184 Mvar² and R² = 0.982; in testing, R² = 0.975, Mean Absolute Error = 11.2 Mvar, and the median error of winter peaks did not exceed 3%. In simulations, the algorithm maintained cos φ between 0.985 and 0.991 for loads ranging from 0.3 to 1.2 p.u., reduced daily losses by 6.1-9.4% (≈1.2 MWh/day), and decreased the number of Static Var Compensator switchings by 38%. Under failure of 20% of Insulated-Gate Bipolar Transistor modules, the duration of cos φ < 0.98 was 0.7%, compared with 19% for the Proportional Integral-Derivative controller. Quantitative comparison of compensation strategies confirmed that the simulated STATCOM-DL system achieved the lowest average cos φ deviations (0.015 vs. 0.030-0.048 for competitors) and minimal annual losses (≈ 430 MWh), outperforming all alternative approaches. The findings confirmed that the combination of deep learning and statistical validation enhances network stability and improves energy efficiency. The practical significance lies in the fact that the resulting algorithms may be employed by railway dispatch centres and energy integrators for real-time optimisation

Authors

Publication Details

Journal
Jornal of Kryvyi Rih National University
Published
2025-11-09
DOI
https://doi.org/10.31721/2306-5451-2025-2-23-34-45
Primary Topic
Railway Systems and Energy Efficiency
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Application of artificial intelligence for optimal control of reactive power compensation in AC traction power supply systems

Maksym Shpilievyi
Jornal of Kryvyi Rih National University
Railway Systems and Energy Efficiency
article

Application of artificial intelligence for optimal control of reactive power compensation in AC traction power supply systems

Maksym Shpilievyi
article en

Abstract

The study aimed to quantitatively assess the effectiveness of neural network-based control of dynamic reactive power compensation in the traction network of Ukrzaliznytsia. The methodology involved high-frequency monitoring of 118 substations (≈16 trillion measurements), aggregation of 52 million Supervisory Control and Data Acquisition records, Theil-Sen trend estimation, Seasonal-Trend decomposition using Loess, the Brown Forsythe test, and a deep neural network with 64-32-16 layers optimised through a Tree-structured Parzen Estimator, validated in 120 Monte Carlo scenarios in Simscape. The results demonstrated that the average daily Q increased from 309.8 to 367.2 Mvar (18.5%) with a trend of 0.95 Mvar/month (95% CI 0.82-1.08; p < 0.001). Winter peaks reached 520 Mvar, while variance after February 2022 increased 1.5-fold (F = 34.9; p < 0.001). The neural network achieved Mean Squared Error = 184 Mvar² and R² = 0.982; in testing, R² = 0.975, Mean Absolute Error = 11.2 Mvar, and the median error of winter peaks did not exceed 3%. In simulations, the algorithm maintained cos φ between 0.985 and 0.991 for loads ranging from 0.3 to 1.2 p.u., reduced daily losses by 6.1-9.4% (≈1.2 MWh/day), and decreased the number of Static Var Compensator switchings by 38%. Under failure of 20% of Insulated-Gate Bipolar Transistor modules, the duration of cos φ < 0.98 was 0.7%, compared with 19% for the Proportional Integral-Derivative controller. Quantitative comparison of compensation strategies confirmed that the simulated STATCOM-DL system achieved the lowest average cos φ deviations (0.015 vs. 0.030-0.048 for competitors) and minimal annual losses (≈ 430 MWh), outperforming all alternative approaches. The findings confirmed that the combination of deep learning and statistical validation enhances network stability and improves energy efficiency. The practical significance lies in the fact that the resulting algorithms may be employed by railway dispatch centres and energy integrators for real-time optimisation

Jornal of Kryvyi Rih National UniversityVol. 23(2)
Affordable and clean energy
Openalex Percentile: Top 28%
Railway Systems and Energy Efficiency
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.