Experimental Investigation of the Ultimate and Service Shear Strength of the Bolted Clip‐Angle Connector in a CFS Beam‐to‐Column Connection

Abstract The present research endeavours to experimentally evaluate the ultimate and service shear strength of the cold‐formed steel (CFS) bolted clip‐angle connector in a CFS beam‐to‐column connection. A total of 58 laboratory tests were conducted on the 27 configurations of the clip‐angle by varying its thickness and aspect ratio (L/D). The governing failure modes observed in the two‐bolted clip‐angle are (i) Tearing and (ii) Shear local buckling. An improved ultimate shear capacity, which accounts for the pitch and slenderness ratios of the clip‐angle connector and the service shear capacity of the clip‐angle connector while accounting for clip‐angle configuration and material properties, was suggested for two bolted (2BS) beam‐to‐column connections. A 2BS connection with L/D ≤ 0.24 is recommended for high shear load design. A comparative study was conducted between the present bolted clip‐angle configuration and the existing screwed configuration. The design factors of Load and Resistance Factor Design (LRFD), Limit State Design (LSD), and Allowable Strength Design (ASD) methods were evaluated for the proposed shear equations by the reliability analysis.

Authors

Institutions

Publication Details

Journal
ce/papers
Published
2025-12-01
DOI
https://doi.org/10.1002/cepa.70185
Primary Topic
Structural Load-Bearing Analysis
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Experimental Investigation of the Ultimate and Service Shear Strength of the Bolted Clip‐Angle Connector in a CFS Beam‐to‐Column Connection

Mahendrakumar Madhavan, Nagaraju Mallepogu, Ranjithkumar Palaniyammal Madheswaran
ce/papers
Structural Load-Bearing Analysis
article

Experimental Investigation of the Ultimate and Service Shear Strength of the Bolted Clip‐Angle Connector in a CFS Beam‐to‐Column Connection

Mahendrakumar Madhavan, Nagaraju Mallepogu, Ranjithkumar Palaniyammal Madheswaran
article en

Abstract

Abstract The present research endeavours to experimentally evaluate the ultimate and service shear strength of the cold‐formed steel (CFS) bolted clip‐angle connector in a CFS beam‐to‐column connection. A total of 58 laboratory tests were conducted on the 27 configurations of the clip‐angle by varying its thickness and aspect ratio (L/D). The governing failure modes observed in the two‐bolted clip‐angle are (i) Tearing and (ii) Shear local buckling. An improved ultimate shear capacity, which accounts for the pitch and slenderness ratios of the clip‐angle connector and the service shear capacity of the clip‐angle connector while accounting for clip‐angle configuration and material properties, was suggested for two bolted (2BS) beam‐to‐column connections. A 2BS connection with L/D ≤ 0.24 is recommended for high shear load design. A comparative study was conducted between the present bolted clip‐angle configuration and the existing screwed configuration. The design factors of Load and Resistance Factor Design (LRFD), Limit State Design (LSD), and Allowable Strength Design (ASD) methods were evaluated for the proposed shear equations by the reliability analysis.

ce/papersVol. 8(6)
Indian Institute of Technology Hyderabad (IN)
Openalex Percentile: Top 33%
Structural Load-Bearing Analysis
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.