Research on Disturbance Factors of Transformer Insulation Using Submersible Internal Inspection Robot

Large oil-immersed power transformers are core equipment in power grids, and the use of robots for internal inspection can significantly enhance efficiency. However, existing research has primarily focused on the development of robotic bodies, neglecting the potential impact of their operation on the transformer’s oil–paper insulation system. This paper addresses this issue, evaluates the risk of underwater inspection robots colliding with internal structures, and finds that the maximum elongation rate of insulation paperboard at a speed of 0.1 m/s is far below the damage limit. Simultaneously, it analyzes the process by which propellers induce bubbles in oil, pointing out the need to optimize propeller design to ensure insulation safety. The study also extends the classical cavitation theory in water to the oil medium, reveals the conditions for gas generation by the propeller and the variation in the patterns of gas components (such as C2H2, H2, etc.) through experiments, and discusses the gas source issue of cavitation in oil.

Authors

Institutions

Publication Details

Journal
Energies
Published
2026-01-23
DOI
https://doi.org/10.3390/en19030581
Primary Topic
Power Line Inspection Robots
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Research on Disturbance Factors of Transformer Insulation Using Submersible Internal Inspection Robot

Wenbin Zhao, Lei Su
Energies
Power Line Inspection Robots
article

Research on Disturbance Factors of Transformer Insulation Using Submersible Internal Inspection Robot

Wenbin Zhao, Lei Su
article en

Abstract

Large oil-immersed power transformers are core equipment in power grids, and the use of robots for internal inspection can significantly enhance efficiency. However, existing research has primarily focused on the development of robotic bodies, neglecting the potential impact of their operation on the transformer’s oil–paper insulation system. This paper addresses this issue, evaluates the risk of underwater inspection robots colliding with internal structures, and finds that the maximum elongation rate of insulation paperboard at a speed of 0.1 m/s is far below the damage limit. Simultaneously, it analyzes the process by which propellers induce bubbles in oil, pointing out the need to optimize propeller design to ensure insulation safety. The study also extends the classical cavitation theory in water to the oil medium, reveals the conditions for gas generation by the propeller and the variation in the patterns of gas components (such as C2H2, H2, etc.) through experiments, and discusses the gas source issue of cavitation in oil.

EnergiesVol. 19(3)
Shanghai University of Electric Power (CN), Shanghai Electric (China) (CN)
Openalex Percentile: Top 80%
Power Line Inspection Robots
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Research on Disturbance Factors of Transformer Insulation Using Submersible Internal Inspection Robot — Wenbin Zhao, Lei Su · Energies (2026) | TGRS Research Map | TGRS