An experimental study on exposure risks in a double-bed patient room with different air distribution methods

Hospital environments have higher requirements for infection control on the health of occupants. This study aims to compare air distribution effects on reducing healthcare exposure risks in a simulated double-bed patient room, focusing on key parameters such as airflow patterns, heat gain, air distribution methods, and exhaust locations. In the experimental study, tracer gas (SF6) was used to simulate airborne aerosols from an infected patient by a thermal breathing manikin. A four-way nozzle diffuser (ND) for mixing ventilation and a dynamic protective airflow panel system (DPP) for personalized ventilation were utilized and compared as two different air distribution methods. The results showed that cases with a high airflow rate of 80 L/s decreased the concentration level, from an average of 22.8-26.5 ppm to 10.5-12.3 ppm compared to conditions with a lower rate of 40 L/s. In addition, the standard deviation (SD) of concentration was 3.5 and 1.1 ppm using DPP with 80 L/s airflow rate under a heat gain level of 17 W/m2 and 29 W/m2, presenting a stable concentration with high heat gains. The dilution ratios for ND and DPP fluctuated at the airflow rate of 80 L/s. While with low airflow rate of 40 L/s, they had no significant differences in removing particles. Exhaust locations did not affect contamination removal in the double-bed patient room.

Authors

Publication Details

Journal
Springer Link (Chiba Institute of Technology)
Published
2026-01-21
DOI
https://doi.org/10.1051/e3sconf/202668905008/pdf
Primary Topic
Infection Control and Ventilation
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

An experimental study on exposure risks in a double-bed patient room with different air distribution methods

Kim Hagström, Simo Kilpeläinen, Jukka Vasara, Jixuan Bao et al.
Springer Link (Chiba Institute of Technology)
Infection Control and Ventilation
article

An experimental study on exposure risks in a double-bed patient room with different air distribution methods

Kim Hagström, Simo Kilpeläinen, Jukka Vasara, Jixuan Bao, Risto Kosonen
article en

Abstract

Hospital environments have higher requirements for infection control on the health of occupants. This study aims to compare air distribution effects on reducing healthcare exposure risks in a simulated double-bed patient room, focusing on key parameters such as airflow patterns, heat gain, air distribution methods, and exhaust locations. In the experimental study, tracer gas (SF6) was used to simulate airborne aerosols from an infected patient by a thermal breathing manikin. A four-way nozzle diffuser (ND) for mixing ventilation and a dynamic protective airflow panel system (DPP) for personalized ventilation were utilized and compared as two different air distribution methods. The results showed that cases with a high airflow rate of 80 L/s decreased the concentration level, from an average of 22.8-26.5 ppm to 10.5-12.3 ppm compared to conditions with a lower rate of 40 L/s. In addition, the standard deviation (SD) of concentration was 3.5 and 1.1 ppm using DPP with 80 L/s airflow rate under a heat gain level of 17 W/m2 and 29 W/m2, presenting a stable concentration with high heat gains. The dilution ratios for ND and DPP fluctuated at the airflow rate of 80 L/s. While with low airflow rate of 40 L/s, they had no significant differences in removing particles. Exhaust locations did not affect contamination removal in the double-bed patient room.

Springer Link (Chiba Institute of Technology)
Good health and well-being
Openalex Percentile: Top 81%
Infection Control and Ventilation
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.