Characteristics of Overvoltages in 500  <scp>kV</scp> Gas‐Insulated Switchgears Caused by Multiple Direct Lightning Strokes

Generally, lightning protection design for a substation has been mainly based on the lightning overvoltage caused by a back flashover occurring at a transmission tower near a substation. It has been reported that electrical breakdown occurred between the moving and fixed contacts of a 500‐kV gas circuit breaker (GCB) because of multiple direct lightning strokes. In a previous study, installing an additional lightning surge arrester (SA) close to the GCB was proposed to protect the GCB from steep‐front subsequent lightning stroke currents. However, no lightning surge analysis for gas‐insulated switchgears (GISs) considering multiple direct lightning strokes has been performed. In order to evaluate the need for countermeasures for GISs against multiple direct strokes, the lightning surge analysis results carried out for a 500‐kV GIS are presented in this paper. © 2026 Institute of Electrical Engineers of Japan and Wiley Periodicals LLC.

Authors

Institutions

Publication Details

Journal
IEEJ Transactions on Electrical and Electronic Engineering
Published
2026-01-21
DOI
https://doi.org/10.1002/tee.70254
Primary Topic
Lightning and Electromagnetic Phenomena
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Characteristics of Overvoltages in 500  kV Gas‐Insulated Switchgears Caused by Multiple Direct Lightning Strokes

Tsuboi Toshihiro, Takashi Yamamoto, Baba Yoshihiro
IEEJ Transactions on Electrical and Electronic Engineering
Lightning and Electromagnetic Phenomena
article

Characteristics of Overvoltages in 500  kV Gas‐Insulated Switchgears Caused by Multiple Direct Lightning Strokes

Tsuboi Toshihiro, Takashi Yamamoto, Baba Yoshihiro
article en

Abstract

Generally, lightning protection design for a substation has been mainly based on the lightning overvoltage caused by a back flashover occurring at a transmission tower near a substation. It has been reported that electrical breakdown occurred between the moving and fixed contacts of a 500‐kV gas circuit breaker (GCB) because of multiple direct lightning strokes. In a previous study, installing an additional lightning surge arrester (SA) close to the GCB was proposed to protect the GCB from steep‐front subsequent lightning stroke currents. However, no lightning surge analysis for gas‐insulated switchgears (GISs) considering multiple direct lightning strokes has been performed. In order to evaluate the need for countermeasures for GISs against multiple direct strokes, the lightning surge analysis results carried out for a 500‐kV GIS are presented in this paper. © 2026 Institute of Electrical Engineers of Japan and Wiley Periodicals LLC.

IEEJ Transactions on Electrical and Electronic Engineering
TEPCO (Japan) (JP), Doshisha University (JP)
Affordable and clean energy
Openalex Percentile: Top 79%
Lightning and Electromagnetic Phenomena
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.