Comprehensive assessment of power quality in a low-voltage node with distributed generation and energy storage: evidence from field monitoring

<ns0:p>The objective of this study is to conduct a comprehensive assessment of power quality parameters in a low-voltage node incorporating photovoltaic modules and an energy storage system, based on long-term field monitoring. The methodology involved analyzing time series of voltages, currents, active power, power factor, and total harmonic distortion recorded with a 15-minute resolution during the period September 2024 – March 2025. Data were segmented according to import and export modes of energy flow, resampled, and subjected to event-based detection of intervals deviating from EN 50160 and IEEE 519 standards. The results demonstrated that voltage consistently remained within permissible limits, whereas approximately 81% of measurements indicated current harmonic distortion exceeding 5%. The absolute power factor was not lower than 0.9 in 90% of cases, but declined to 0.85–0.90 in nearly 10% of intervals, primarily due to harmonic distortion and reactive power exchange. Moreover, the analysis confirmed the high stiffness of the supply network, which accounts for the stability of voltage parameters despite pronounced current harmonics. The findings underline the necessity of implementing active or passive filtering measures to mitigate harmonic distortion and maintain power factor stability.</ns0:p>

Authors

Publication Details

Journal
Energy and automation
Published
2025-11-02
DOI
https://doi.org/10.31548/energiya5(81).2025.114
Primary Topic
Power Quality and Harmonics
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Comprehensive assessment of power quality in a low-voltage node with distributed generation and energy storage: evidence from field monitoring

A. Raichenko
Energy and automation
Power Quality and Harmonics
article

Comprehensive assessment of power quality in a low-voltage node with distributed generation and energy storage: evidence from field monitoring

A. Raichenko
article en

Abstract

<ns0:p>The objective of this study is to conduct a comprehensive assessment of power quality parameters in a low-voltage node incorporating photovoltaic modules and an energy storage system, based on long-term field monitoring. The methodology involved analyzing time series of voltages, currents, active power, power factor, and total harmonic distortion recorded with a 15-minute resolution during the period September 2024 – March 2025. Data were segmented according to import and export modes of energy flow, resampled, and subjected to event-based detection of intervals deviating from EN 50160 and IEEE 519 standards. The results demonstrated that voltage consistently remained within permissible limits, whereas approximately 81% of measurements indicated current harmonic distortion exceeding 5%. The absolute power factor was not lower than 0.9 in 90% of cases, but declined to 0.85–0.90 in nearly 10% of intervals, primarily due to harmonic distortion and reactive power exchange. Moreover, the analysis confirmed the high stiffness of the supply network, which accounts for the stability of voltage parameters despite pronounced current harmonics. The findings underline the necessity of implementing active or passive filtering measures to mitigate harmonic distortion and maintain power factor stability.</ns0:p>

Energy and automation
Affordable and clean energy
Openalex Percentile: Top 38%
Power Quality and Harmonics
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.