A longitudinal study of CO2 and air exchange rate variations in naturally ventilated airtight energy-efficient dwellings

Background: In energy-efficient dwellings, the relationship between airtightness and natural ventilation is critical but underexplored. As airtightness increases, the ability of natural ventilation to provide adequate ventilation may diminish, potentially compromising Indoor Environmental Quality (IEQ). Aim: This study provides a unique assessment of ventilation performance in energy-efficient, naturally ventilated, airtight dwellings, with a particular focus on the impact of long-term variations on indoor CO2 levels and Air Exchange Rate (AER). Methodology: A novel longitudinal approach used a decay method based on occupant-generated CO2 to estimate AER. CO2 concentrations were monitored in nine Irish homes over one year, followed by annual and seasonal assessments. Results: The findings revealed clear long-term and seasonal variations in ventilation performance. Winter CO2 concentrations were consistently higher, indicating reduced ventilation due to lower window use. The seasonal median AER range was 0.15 h~ 1 (winter) to 0.27 h~ 1 (summer), reflecting poor ventilation during colder periods. Over 51 % of AER values fell within 0.1–0.3 h~ 1, and 15 % were below 0.1 h~ 1, suggesting persistent under-ventilation. Only 0.4 % of values exceeded 1.0 h~ 1. The mean AER (0.28 h~ 1) was 42–70 % lower than in conventional dwellings, reinforcing the inadequacy of natural ventilation strategies over time. Purge ventilation events were infrequent and short-lived, with transient rates of 0.4–2.7 h~ 1. Conclusion: The study underscores the need for adaptive ventilation strategies in energy-efficient buildings, particularly in colder months. While natural ventilation can provide adequate rates, improvements such as hybrid systems and occupant education are recommended for optimising ventilation.

Authors

Publication Details

Journal
Journal of Building Engineering
Published
2026-01-13
DOI
https://doi.org/10.1016/j.jobe.2026.115257
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

A longitudinal study of CO2 and air exchange rate variations in naturally ventilated airtight energy-efficient dwellings

Divyanshu Sood, Miriam Byrne, James O’Donnell, Ibrahim Alhindawi et al.
Journal of Building Engineering
Building Energy and Comfort Optimization
article

A longitudinal study of CO2 and air exchange rate variations in naturally ventilated airtight energy-efficient dwellings

Divyanshu Sood, Miriam Byrne, James O’Donnell, Ibrahim Alhindawi, Jorge M. Fernandes
article en

Abstract

Background: In energy-efficient dwellings, the relationship between airtightness and natural ventilation is critical but underexplored. As airtightness increases, the ability of natural ventilation to provide adequate ventilation may diminish, potentially compromising Indoor Environmental Quality (IEQ). Aim: This study provides a unique assessment of ventilation performance in energy-efficient, naturally ventilated, airtight dwellings, with a particular focus on the impact of long-term variations on indoor CO2 levels and Air Exchange Rate (AER). Methodology: A novel longitudinal approach used a decay method based on occupant-generated CO2 to estimate AER. CO2 concentrations were monitored in nine Irish homes over one year, followed by annual and seasonal assessments. Results: The findings revealed clear long-term and seasonal variations in ventilation performance. Winter CO2 concentrations were consistently higher, indicating reduced ventilation due to lower window use. The seasonal median AER range was 0.15 h~ 1 (winter) to 0.27 h~ 1 (summer), reflecting poor ventilation during colder periods. Over 51 % of AER values fell within 0.1–0.3 h~ 1, and 15 % were below 0.1 h~ 1, suggesting persistent under-ventilation. Only 0.4 % of values exceeded 1.0 h~ 1. The mean AER (0.28 h~ 1) was 42–70 % lower than in conventional dwellings, reinforcing the inadequacy of natural ventilation strategies over time. Purge ventilation events were infrequent and short-lived, with transient rates of 0.4–2.7 h~ 1. Conclusion: The study underscores the need for adaptive ventilation strategies in energy-efficient buildings, particularly in colder months. While natural ventilation can provide adequate rates, improvements such as hybrid systems and occupant education are recommended for optimising ventilation.

Journal of Building EngineeringVol. 119
Affordable and clean energy
Openalex Percentile: Top 90%
Building Energy and Comfort Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.