Fast Fault Identification Scheme for MMC-HVDC Grids Based on a Novel Current-Limiting DC Circuit Breaker

The development of high-performance DC circuit breakers (DCCBs) and rapid fault detection schemes is a crucial and challenging part of advancing Modular Multilevel Converter (MMC) HVDC grids. This paper introduces a new current-limiting DCCB that uses the differential discharge times of shunt capacitors to generate artificial current zero-crossings, thus facilitating arc quenching. This mechanism significantly reduces the effect of fault currents on the MMC. The shunt capacitors and arresters in the proposed breaker also offer voltage support during faults, effectively stopping transient traveling waves from spreading to nearby non-fault lines. This feature creates an effective line protection boundary in multi-terminal HVDC systems. Additionally, a fast fault detection scheme with primary and backup protection is proposed. A four-terminal MMC-HVDC (±500 kV) simulation model is built in PSCAD/EMTDC to validate the scheme. The results demonstrate the excellent fault detection performance of the proposed method. The voltage and current behavior during the interruption process of the new DCCB is also analyzed and compared with that of a hybrid DCCB.

Authors

Institutions

Publication Details

Journal
Energies
Published
2026-01-05
DOI
https://doi.org/10.3390/en19010272
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Fast Fault Identification Scheme for MMC-HVDC Grids Based on a Novel Current-Limiting DC Circuit Breaker

Xiuyong Yu Xiuyong Yu, Xinsong Zhang, Zhiyan Li, Chenghong Gu et al.
Energies
HVDC Systems and Fault Protection
article

Fast Fault Identification Scheme for MMC-HVDC Grids Based on a Novel Current-Limiting DC Circuit Breaker

Xiuyong Yu Xiuyong Yu, Xinsong Zhang, Zhiyan Li, Chenghong Gu, Qiuyu Cao
article en

Abstract

The development of high-performance DC circuit breakers (DCCBs) and rapid fault detection schemes is a crucial and challenging part of advancing Modular Multilevel Converter (MMC) HVDC grids. This paper introduces a new current-limiting DCCB that uses the differential discharge times of shunt capacitors to generate artificial current zero-crossings, thus facilitating arc quenching. This mechanism significantly reduces the effect of fault currents on the MMC. The shunt capacitors and arresters in the proposed breaker also offer voltage support during faults, effectively stopping transient traveling waves from spreading to nearby non-fault lines. This feature creates an effective line protection boundary in multi-terminal HVDC systems. Additionally, a fast fault detection scheme with primary and backup protection is proposed. A four-terminal MMC-HVDC (±500 kV) simulation model is built in PSCAD/EMTDC to validate the scheme. The results demonstrate the excellent fault detection performance of the proposed method. The voltage and current behavior during the interruption process of the new DCCB is also analyzed and compared with that of a hybrid DCCB.

EnergiesVol. 19(1)
Nantong University (CN), University of Bath (GB)
National Natural Science Foundation of China
Openalex Percentile: Top 97%
HVDC Systems and Fault Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.