Basic Study on Fire Detection Using Air Temperature Monitoring with an Ultrasonic Probe
This paper reports on a fire detection method using an ultrasonic probe that measures room temperature based on the speed of sound. We establish the relationship between the time-of-flight (ToF) of acoustic waves and air temperature in the presence of flames. An ultrasonic probe consisting of a speaker and a microphone was developed, and fire experiments were conducted to measure the ToF at multiple flame locations. Results indicate that temperature increases caused by a flame can be detected using acoustic waves. However, the correlation between the transmitted and received waveforms decreases when the acoustic wave passes through the flame, thereby interfering with the cross-correlation function used in the ToF measurement. These findings suggest that the ultrasonic probe has potential for early fire detection in indoor environments by monitoring changes in ToF.
Authors
- Naoto Wakatsuki (ORCID: https://orcid.org/0000-0002-3889-8915)
- Tadashi Ebihara (ORCID: https://orcid.org/0000-0001-5457-6783)
- Manabu Dohi
- Yunosuke Kozumi
Institutions
- University of Tsukuba (JP)
Publication Details
- Journal
- Journal of Signal Processing
- Published
- 2025-12-31
- DOI
- https://doi.org/10.2299/jsp.30.23
- Primary Topic
- Fire Detection and Safety Systems
- Type
- article
- Field-Weighted Citation Impact
- 0.00