Modeling an Industrial Distribution Network with Significant Photovoltaic Integration Using ATP-EMTP
This article presents an analysis of the impact of photovoltaic (PV) sources on the effectiveness and selectivity of earth fault protection in a 6 kV industrial distribution network. Simulations were conducted in the ATP-EMTP environment using a model of a generalized, real industrial network with an isolated neutral point. This model was based on data from real-world cases of earth faults with varying resistance. This study’s main objective was to determine how the power generated by PV sources affects the time and spectral waveforms of currents and zero-sequence voltages, in addition to the network’s overall response to disturbances. The results provide a quantitative assessment of the impact of distributed generation on the operational security of industrial power grids and form a basis for developing recommendations for coordinating protection in power systems integrated with renewable energy sources.
Authors
- Krzysztof Kuliński (ORCID: https://orcid.org/0000-0002-7968-2184)
- Katarzyna Nowińska
Institutions
- Silesian University of Technology (PL)
Publication Details
- Journal
- Energies
- Published
- 2025-12-30
- DOI
- https://doi.org/10.3390/en19010196
- Primary Topic
- Power Systems Fault Detection
- Type
- article
- Field-Weighted Citation Impact
- 0.00