Оцінка мінімального рівня вищих гармонік струму однофазного замикання на землю у компенсованих мережах 6–10 кВ

Purpose Development of a model for a compensated 6–10 kV network and a methodology for selecting its element parameters based on estimating the minimum level of higher harmonics in the single-phase-to-ground fault current. Methodology. To estimate the minimum level of higher harmonics in single-phase-to-ground fault current currents, a generalized model of a compensated 6–10 kV cable network and its constituent elements, implemented in the Matlab system with the Simulink extension package, was used. The generalized model of the compensated 6–10 kV cable network and its element parameters were obtained based on a statistical analysis of data from the power supply systems of cities and industrial enterprises. Findings. The main requirements for the equivalent calculation scheme of a 6–10 kV cable network for estimating the minimum level of higher harmonics in the single-phase-to-ground fault current were formulated, and the ranges of variation and average values of its parameters were determined. The developed mathematical model of the 6–10 kV cable network accounts for the main factors determining the minimum level of higher harmonics in the single-phase-to-ground fault current. Based on the results of computational experiments performed on the mathematical models of 6–10 kV cable networks, it was established that to ensure the required sensitivity, single-phase-to-ground fault protection devices based on the use of higher harmonics must have a primary pickup current of no more than 0.1A. Originality. A model of a compensated 6–10 kV network was developed, which allows clarifying the sensitivity requirements for single-phase-to-ground fault protection systems based on the use of higher harmonics, thereby enhancing their operational efficiency. Practical value. Based on the mathematical model, a methodology for selecting its element parameters is proposed, which utilizes the estimation of the minimum level of higher harmonics in the single-phase-to-ground fault currents.

Authors

Institutions

Publication Details

Journal
The Scientific Issues of Ternopil Volodymyr Hnatiuk National Pedagogical University Series pedagogy
Published
2025-12-26
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Оцінка мінімального рівня вищих гармонік струму однофазного замикання на землю у компенсованих мережах 6–10 кВ

А.Є. Шамрай, І.В. Ісаєв
The Scientific Issues of Ternopil Volodymyr Hnatiuk National Pedagogical University Series pedagogy
Power Systems Fault Detection
article

Оцінка мінімального рівня вищих гармонік струму однофазного замикання на землю у компенсованих мережах 6–10 кВ

А.Є. Шамрай, І.В. Ісаєв
article en

Abstract

Purpose Development of a model for a compensated 6–10 kV network and a methodology for selecting its element parameters based on estimating the minimum level of higher harmonics in the single-phase-to-ground fault current. Methodology. To estimate the minimum level of higher harmonics in single-phase-to-ground fault current currents, a generalized model of a compensated 6–10 kV cable network and its constituent elements, implemented in the Matlab system with the Simulink extension package, was used. The generalized model of the compensated 6–10 kV cable network and its element parameters were obtained based on a statistical analysis of data from the power supply systems of cities and industrial enterprises. Findings. The main requirements for the equivalent calculation scheme of a 6–10 kV cable network for estimating the minimum level of higher harmonics in the single-phase-to-ground fault current were formulated, and the ranges of variation and average values of its parameters were determined. The developed mathematical model of the 6–10 kV cable network accounts for the main factors determining the minimum level of higher harmonics in the single-phase-to-ground fault current. Based on the results of computational experiments performed on the mathematical models of 6–10 kV cable networks, it was established that to ensure the required sensitivity, single-phase-to-ground fault protection devices based on the use of higher harmonics must have a primary pickup current of no more than 0.1A. Originality. A model of a compensated 6–10 kV network was developed, which allows clarifying the sensitivity requirements for single-phase-to-ground fault protection systems based on the use of higher harmonics, thereby enhancing their operational efficiency. Practical value. Based on the mathematical model, a methodology for selecting its element parameters is proposed, which utilizes the estimation of the minimum level of higher harmonics in the single-phase-to-ground fault currents.

The Scientific Issues of Ternopil Volodymyr Hnatiuk National Pedagogical University Series pedagogy
National University Zaporizhzhia Polytechnic (UA)
Sustainable cities and communities
Openalex Percentile: Top 36%
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.