On-Site Sound Pressure Level Evaluation of Emergency Broadcasting Systems in University Buildings

Korean regulations for emergency broadcasting systems specify only the rated power output of loudspeakers: 1 W for indoor and 3 W for outdoor applications. However, they do not provide quantitative sound pressure level (SPL) criteria. In this study, A-weighted SPLs in nine buildings at a university were measured and analyzed by reproducing actual emergency broadcast signals. The measured SPLs ranged from 51 dB (A) to 99 dB (A), indicating a difference of approximately 20 dB (A) between the lowest and highest average values across the buildings. In addition, the alarm tone exhibited SPLs approximately 20 dB (A) higher than those of the voice message, representing a perceptual loudness difference exceeding fourfold. These results confirm that despite the installation of emergency broadcasting systems adhering to power-based criteria, the loudness experienced by occupants can vary substantially depending on the spatial characteristics and specific measurement zones within buildings. Consequently, regulatory provisions based solely on loudspeaker power output are inadequate for ensuring consistent audibility in emergency broadcasts. This indicates the need for quantitative SPL criteria to ensure adequate occupant perception performance.

Authors

Publication Details

Journal
Fire Science and Engineering
Published
2025-12-26
DOI
https://doi.org/10.7731/kifse.c00f1f0a
Primary Topic
Hearing Loss and Rehabilitation
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

On-Site Sound Pressure Level Evaluation of Emergency Broadcasting Systems in University Buildings

Ji-Won Gu, Jun-Ho Choi
Fire Science and Engineering
Hearing Loss and Rehabilitation
article

On-Site Sound Pressure Level Evaluation of Emergency Broadcasting Systems in University Buildings

Ji-Won Gu, Jun-Ho Choi
article en

Abstract

Korean regulations for emergency broadcasting systems specify only the rated power output of loudspeakers: 1 W for indoor and 3 W for outdoor applications. However, they do not provide quantitative sound pressure level (SPL) criteria. In this study, A-weighted SPLs in nine buildings at a university were measured and analyzed by reproducing actual emergency broadcast signals. The measured SPLs ranged from 51 dB (A) to 99 dB (A), indicating a difference of approximately 20 dB (A) between the lowest and highest average values across the buildings. In addition, the alarm tone exhibited SPLs approximately 20 dB (A) higher than those of the voice message, representing a perceptual loudness difference exceeding fourfold. These results confirm that despite the installation of emergency broadcasting systems adhering to power-based criteria, the loudness experienced by occupants can vary substantially depending on the spatial characteristics and specific measurement zones within buildings. Consequently, regulatory provisions based solely on loudspeaker power output are inadequate for ensuring consistent audibility in emergency broadcasts. This indicates the need for quantitative SPL criteria to ensure adequate occupant perception performance.

Fire Science and EngineeringVol. 39(6)
Sustainable cities and communities
Openalex Percentile: Top 32%
Hearing Loss and Rehabilitation
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

On-Site Sound Pressure Level Evaluation of Emergency Broadcasting Systems in University Buildings — Ji-Won Gu, Jun-Ho Choi · Fire Science and Engineering (2025) | TGRS Research Map | TGRS