Design of Fault Protection Stra for Unified Power Flow Controller in Distribution Networks

The capacity of traditional distribution networks is limited. After large-scale distributed power sources are connected, it is difficult to consume them at the same voltage level, which can lead to transformer reverse overloading and voltage limit violations. Although the unified power flow controller (UPFC) excels in flexible power flow regulation and power quality optimization, existing research on it is mostly focused on the transmission grid, focusing on device topology, power flow control, etc. Fault protection is also targeted at high-voltage and ultra-high-voltage domains and only covers a single overvoltage or overcurrent fault. Research on the protection of the unified power flow controller in a distribution network (D-UPFC) remains scarce. A key challenge is the absence of fault protection schemes that are compatible with the unified power flow controller in a distribution network, which cannot meet the requirements of the distribution network for monitoring and protecting multiple fault types, rapid response, and equipment economy. This paper first designs a protection device centered on the distribution thyristor bypass switch (D-TBS), completes the thyristor selection and transient energy extraction, optimizes the overvoltage protection loop parameter, then builds a three-level coordinated protection architecture, and, finally, verifies through functional and system tests. The results show that the thyristor control unit trigger is reliable and the total overvoltage response delay is 1.08 μs. In the case of a three-phase short-circuit fault in a 600 kVA/10 kV system, the distribution thyristor bypass switch can rapidly reduce the secondary voltage of the series transformer, suppress transient overcurrent, achieve isolation protection of the main equipment, provide a reliable guarantee for the engineering application of the distribution network unified power flow controller, and expand its distribution network application scenarios.

Authors

Institutions

Publication Details

Journal
Energies
Published
2025-12-23
DOI
https://doi.org/10.3390/en19010079
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Design of Fault Protection Stra for Unified Power Flow Controller in Distribution Networks

Xiaochun Mou, Wu Chen, Kai Wang, Jilong Song et al.
Energies
Power Systems Fault Detection
article

Design of Fault Protection Stra for Unified Power Flow Controller in Distribution Networks

Xiaochun Mou, Wu Chen, Kai Wang, Jilong Song, Xinran Huo, Xuejun Zhang, Ruijun Zhu
article en

Abstract

The capacity of traditional distribution networks is limited. After large-scale distributed power sources are connected, it is difficult to consume them at the same voltage level, which can lead to transformer reverse overloading and voltage limit violations. Although the unified power flow controller (UPFC) excels in flexible power flow regulation and power quality optimization, existing research on it is mostly focused on the transmission grid, focusing on device topology, power flow control, etc. Fault protection is also targeted at high-voltage and ultra-high-voltage domains and only covers a single overvoltage or overcurrent fault. Research on the protection of the unified power flow controller in a distribution network (D-UPFC) remains scarce. A key challenge is the absence of fault protection schemes that are compatible with the unified power flow controller in a distribution network, which cannot meet the requirements of the distribution network for monitoring and protecting multiple fault types, rapid response, and equipment economy. This paper first designs a protection device centered on the distribution thyristor bypass switch (D-TBS), completes the thyristor selection and transient energy extraction, optimizes the overvoltage protection loop parameter, then builds a three-level coordinated protection architecture, and, finally, verifies through functional and system tests. The results show that the thyristor control unit trigger is reliable and the total overvoltage response delay is 1.08 μs. In the case of a three-phase short-circuit fault in a 600 kVA/10 kV system, the distribution thyristor bypass switch can rapidly reduce the secondary voltage of the series transformer, suppress transient overcurrent, achieve isolation protection of the main equipment, provide a reliable guarantee for the engineering application of the distribution network unified power flow controller, and expand its distribution network application scenarios.

EnergiesVol. 19(1)
Qingdao University (CN), NARI Group (China) (CN), Southeast University (CN)
Affordable and clean energy
Openalex Percentile: Top 37%
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.