Modeling moisture buffering of innovative plasters from material properties to room scale

Passive moisture buffering can stabilize indoor microclimates and reduce cooling energy use, yet reliable prediction across scales remains challenging. This study presents a simplified characterization-to-modeling workflow that links laboratory measurements to room-scale performance. Step-response tests in a dynamic vapour sorption (DVS) analyzer were interpreted with a Fickian diffusion model fitted via root-mean-square error minimization, yielding effective moisture diffusivities of D≈1.84×10 −8 m 2 s −1 for the lime plaster and D≈1.17×10 −9 m 2 s −1 for a plaster containing 20% calcium alginate beads. Vapour-resistance factor functions derived from these fits and from sorption isotherms were validated against NORDTEST MBV dynamic measurements, with the best agreement for both mass change (Δm) and MBV at a surface resistance of 0.1 m 2 KW -1 (errors: 0.67% lime; 1.59% alginate). Year-long building simulations then quantified room-scale impacts: the alginate-enhanced plaster attenuated indoor RH fluctuations more effectively than lime, with attenuation factors spanning from 0.2 to -0.8 depending on the moment of the year and the simulated scenario. Energy analyses showed substantial reductions in latent cooling (up to ∼100% in scenarios with wider indoor relative humidity control band) and up to 11.2% lower total cooling energy versus lime, with similar sensible loads. The results demonstrate a practical, scalable pathway from material properties to performance, and highlight alginate-enhanced plasters as promising passive components for humidity stabilization and energy-efficient building design and retrofits. • A diffusion-based procedure, validated against MBV cycles, for use in WUFI®/Delphin material property estimation. • The method was applied to lime plaster and a plaster enhanced with super-adsorbent alginate spheres. • Validation reproduced dynamic sorption–desorption cycles with ±5% accuracy. • WUFI® Plus simulations are used to assess the moisture buffering effect in an office room. • Alginate plaster mitigated indoor humidity swings and reduced latent cooling demand by up to 100%.

Authors

Institutions

Publication Details

Journal
Journal of Building Engineering
Published
2025-12-23
DOI
https://doi.org/10.1016/j.jobe.2025.114983
Primary Topic
Hygrothermal properties of building materials
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Modeling moisture buffering of innovative plasters from material properties to room scale

V. Gentile, V. Serra, G. Autretto, M. Libralato et al.
Journal of Building Engineering
Hygrothermal properties of building materials
article

Modeling moisture buffering of innovative plasters from material properties to room scale

V. Gentile, V. Serra, G. Autretto, M. Libralato, S. Fantucci
article en

Abstract

Passive moisture buffering can stabilize indoor microclimates and reduce cooling energy use, yet reliable prediction across scales remains challenging. This study presents a simplified characterization-to-modeling workflow that links laboratory measurements to room-scale performance. Step-response tests in a dynamic vapour sorption (DVS) analyzer were interpreted with a Fickian diffusion model fitted via root-mean-square error minimization, yielding effective moisture diffusivities of D≈1.84×10 −8 m 2 s −1 for the lime plaster and D≈1.17×10 −9 m 2 s −1 for a plaster containing 20% calcium alginate beads. Vapour-resistance factor functions derived from these fits and from sorption isotherms were validated against NORDTEST MBV dynamic measurements, with the best agreement for both mass change (Δm) and MBV at a surface resistance of 0.1 m 2 KW -1 (errors: 0.67% lime; 1.59% alginate). Year-long building simulations then quantified room-scale impacts: the alginate-enhanced plaster attenuated indoor RH fluctuations more effectively than lime, with attenuation factors spanning from 0.2 to -0.8 depending on the moment of the year and the simulated scenario. Energy analyses showed substantial reductions in latent cooling (up to ∼100% in scenarios with wider indoor relative humidity control band) and up to 11.2% lower total cooling energy versus lime, with similar sensible loads. The results demonstrate a practical, scalable pathway from material properties to performance, and highlight alginate-enhanced plasters as promising passive components for humidity stabilization and energy-efficient building design and retrofits. • A diffusion-based procedure, validated against MBV cycles, for use in WUFI®/Delphin material property estimation. • The method was applied to lime plaster and a plaster enhanced with super-adsorbent alginate spheres. • Validation reproduced dynamic sorption–desorption cycles with ±5% accuracy. • WUFI® Plus simulations are used to assess the moisture buffering effect in an office room. • Alginate plaster mitigated indoor humidity swings and reduced latent cooling demand by up to 100%.

Journal of Building EngineeringVol. 118
University of Udine (IT), Politecnico di Torino (IT)
Affordable and clean energy
Openalex Percentile: Top 39%
Hygrothermal properties of building materials
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.