Capacity Design Method for Integrated Convective/Radiant Terminals to Guarantee Overall and Local Environment
To achieve energy efficiency in the operation of heating devices and ensure thermal comfort in indoor environments, the integrated convective/radiant terminals have become an important development direction for heating systems. This study selected a 14 m2 bedroom hot summer and cold winter region in China as a case study. Computational Fluid Dynamics (CFD) methodology was used to investigate the design of integrated convective/radiant terminals to ensure thermal comfort for both the entire room and partial space. The results indicate that focusing on partial space during the steady-state stage can achieve energy savings of 31.1% compared to guaranteeing the entire room. Additionally, during the start-up stage, there is a significant reduction of convective unit capacity by 17.6% when the start-up time is 15 minutes. These findings provide data support for the design and engineering applications of products of integrated convective/radiant terminals. Besides, the excess convection ratios for the entire room and partial space are specified as 0.69 to 0.80 and 0.73 to 0.83, respectively.