Power Swing Trajectory Influenced by Virtual Impedance-Based Current-Limiting Strategy

Grid-forming (GFM) inverter-based resources (IBRs) can emulate the external characteristics of synchronous generators (SGs) through appropriate control loop design. However, in systems with GFM IBRs, the apparent impedance trajectory under current limitation differs significantly from that of SG-based systems due to the limited overcurrent capability of power electronic devices. This difference challenges the power swing detection functions of distance relays designed for SG-based systems. This paper presents a theoretical analysis of the apparent impedance trajectory over a full power swing cycle under two typical current-limiting strategies: variable virtual impedance (VI) and adaptive VI. The analysis reveals that the trajectory under VI current-limiting strategies differs significantly from that of a conventional SG. The results also indicate that the control parameters affect the characteristics of the trajectory. In addition, the new trajectories challenge conventional power swing detection functions, increasing the risk of malfunction. Furthermore, the implementation of VI leads to a deterioration in system stability. The theoretical analysis is further validated through simulations on the MATLAB/Simulink platform.

Publication Details

Journal
ArXiv.org
Published
2025-03-15
Primary Topic
Microgrid Control and Optimization
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Power Swing Trajectory Influenced by Virtual Impedance-Based Current-Limiting Strategy

ArXiv.org
Microgrid Control and Optimization
article

Power Swing Trajectory Influenced by Virtual Impedance-Based Current-Limiting Strategy

article en

Abstract

Grid-forming (GFM) inverter-based resources (IBRs) can emulate the external characteristics of synchronous generators (SGs) through appropriate control loop design. However, in systems with GFM IBRs, the apparent impedance trajectory under current limitation differs significantly from that of SG-based systems due to the limited overcurrent capability of power electronic devices. This difference challenges the power swing detection functions of distance relays designed for SG-based systems. This paper presents a theoretical analysis of the apparent impedance trajectory over a full power swing cycle under two typical current-limiting strategies: variable virtual impedance (VI) and adaptive VI. The analysis reveals that the trajectory under VI current-limiting strategies differs significantly from that of a conventional SG. The results also indicate that the control parameters affect the characteristics of the trajectory. In addition, the new trajectories challenge conventional power swing detection functions, increasing the risk of malfunction. Furthermore, the implementation of VI leads to a deterioration in system stability. The theoretical analysis is further validated through simulations on the MATLAB/Simulink platform.

ArXiv.org
Openalex Percentile: Top 45%
Microgrid Control and Optimization
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.