Effect of Moisture and Load Change on Clamping Pressure in a Transformer Test Rig

During the manufacturing of a power transformer, typically, a fixed clamping pressure is exerted on the winding structure to keep its mechanical integrity during short circuit faults. Various factors, e.g., breathing during load cycles, poor sealing, aging of cellulose materials, etc., introduce moisture in the transformer during its long service life. A typical power transformer operation has a continuous moisture exchange between the cellulose material and the oil. The pressboard samples and controllable heated brass plates are stacked in a test rig. This paper investigates the effect of moisture and load variation on the development of clamping pressure in the test rig. Pressboard samples with two different moisture contents are studied: dry (~0.6%) and wet (~4.7%). Two different heating cycles are investigated: a constant load and a frequent start-stop load. The temperature of the brass plate and oil, relative humidity of oil and pressboard, and clamping force are measured throughout the experiment. It has been observed that the clamping pressure follows the temperature profile of the brass plates. A significant loss of clamping pressure is observed after mounting the wet samples in the rig. The clamping pressure drops further after the first heating cycle as the rig temperature returns to the ambient. However, when the rig returns to room temperature, there is no noticeable decrease in clamping pressure, neither for the dry sample nor for the wet sample after its first heating cycle.

Institutions

Publication Details

Published
2024-10-06
DOI
https://doi.org/10.1109/ceidp61745.2024.10907329
Primary Topic
Mycorrhizal Fungi and Plant Interactions
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Effect of Moisture and Load Change on Clamping Pressure in a Transformer Test Rig

Mycorrhizal Fungi and Plant Interactions
article

Effect of Moisture and Load Change on Clamping Pressure in a Transformer Test Rig

article en

Abstract

During the manufacturing of a power transformer, typically, a fixed clamping pressure is exerted on the winding structure to keep its mechanical integrity during short circuit faults. Various factors, e.g., breathing during load cycles, poor sealing, aging of cellulose materials, etc., introduce moisture in the transformer during its long service life. A typical power transformer operation has a continuous moisture exchange between the cellulose material and the oil. The pressboard samples and controllable heated brass plates are stacked in a test rig. This paper investigates the effect of moisture and load variation on the development of clamping pressure in the test rig. Pressboard samples with two different moisture contents are studied: dry (~0.6%) and wet (~4.7%). Two different heating cycles are investigated: a constant load and a frequent start-stop load. The temperature of the brass plate and oil, relative humidity of oil and pressboard, and clamping force are measured throughout the experiment. It has been observed that the clamping pressure follows the temperature profile of the brass plates. A significant loss of clamping pressure is observed after mounting the wet samples in the rig. The clamping pressure drops further after the first heating cycle as the rig temperature returns to the ambient. However, when the rig returns to room temperature, there is no noticeable decrease in clamping pressure, neither for the dry sample nor for the wet sample after its first heating cycle.

SINTEF (NO), Norwegian University of Science and Technology (NO), KTH Royal Institute of Technology (SE)
Affordable and clean energy
Openalex Percentile: Top 59%
Mycorrhizal Fungi and Plant Interactions
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Effect of Moisture and Load Change on Clamping Pressure in a Transformer Test Rig · (2024) | TGRS Research Map | TGRS