OPTIMIZED RELAY COORDINATION FOR SUPERIOR ELECTRICAL PERFORMANCE: LESSONS FROM INDORAMA FERTILIZER AND CHEMICALS

The research addresses the challenge of inadequate relay coordination at the motor control center of Indorama Fertilizer and Chemicals Limited. Utilizing the Electrical Transient Analyzer program (ETAP 19.0.1), the study employs methodologies such as Load Flow Analysis, Short Circuit Analysis, and Relay Setting and Coordination with Standard Inverse Time Delay (SIT) to model and simulate the electrical network. Findings reveal that during a base case scenario, a trip sequence failure occurs when a three-phase short circuit fault arises at the terminal of the synchronous motor labeled (syn1). The backup relay (R4) activates first at 286.5 ms, followed by the primary relay (R6) at 408.1 ms, relay 2 at 630.4 ms, and relay 1 at 864.5 ms. This miscoordination results in a total blackout of the Motor Control Unit (Cmtr1) due to a single downstream fault. To enhance coordination, a new relay setting is proposed, implementing IEC standard inverse characteristics to replace the existing definite-minimum-time (DMT) scheme with a more adaptable inverse-definite-minimum-time (IDMT) scheme. The revised configuration reduces the relay operation time by over 35% compared to the original setup, providing better fault backup and significantly improving the relay's operational sequence and tripping times without major coordination issues

Institutions

Publication Details

Journal
Zenodo (CERN European Organization for Nuclear Research)
Published
2024-09-19
DOI
https://doi.org/10.5281/zenodo.13789830
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

OPTIMIZED RELAY COORDINATION FOR SUPERIOR ELECTRICAL PERFORMANCE: LESSONS FROM INDORAMA FERTILIZER AND CHEMICALS

Zenodo (CERN European Organization for Nuclear Research)
Power Systems Fault Detection
article

OPTIMIZED RELAY COORDINATION FOR SUPERIOR ELECTRICAL PERFORMANCE: LESSONS FROM INDORAMA FERTILIZER AND CHEMICALS

article en

Abstract

The research addresses the challenge of inadequate relay coordination at the motor control center of Indorama Fertilizer and Chemicals Limited. Utilizing the Electrical Transient Analyzer program (ETAP 19.0.1), the study employs methodologies such as Load Flow Analysis, Short Circuit Analysis, and Relay Setting and Coordination with Standard Inverse Time Delay (SIT) to model and simulate the electrical network. Findings reveal that during a base case scenario, a trip sequence failure occurs when a three-phase short circuit fault arises at the terminal of the synchronous motor labeled (syn1). The backup relay (R4) activates first at 286.5 ms, followed by the primary relay (R6) at 408.1 ms, relay 2 at 630.4 ms, and relay 1 at 864.5 ms. This miscoordination results in a total blackout of the Motor Control Unit (Cmtr1) due to a single downstream fault. To enhance coordination, a new relay setting is proposed, implementing IEC standard inverse characteristics to replace the existing definite-minimum-time (DMT) scheme with a more adaptable inverse-definite-minimum-time (IDMT) scheme. The revised configuration reduces the relay operation time by over 35% compared to the original setup, providing better fault backup and significantly improving the relay's operational sequence and tripping times without major coordination issues

Zenodo (CERN European Organization for Nuclear Research)
Rivers State University (NG)
Openalex Percentile: Top 58%
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.