Integration of cryogenic exergy from liquid hydrogen into data center operation using an organic Rankine cycle

This study investigates the integration of cryogenic exergy of liquid hydrogen into data center power saving and cooling using an organic Rankine cycle (ORC). In the proposed system, the cryogenic exergy is first utilized for supplementary power generation and then for supplying low-temperature cooling, resulting in improved overall energy efficiency. Parametric analyses were conducted to evaluate the effects of hydrogen supply conditions on overall system performance. As the inlet temperature of liquid hydrogen decreased to 20 K, both the net power output and cooling capacity increased, reducing the power usage effectiveness (PUE) to 1.30. Increasing the mass flow rate of liquid hydrogen further improved the total energy efficiency to 69.2% and decreased the PUE to 1.14. Working fluid optimization using particle swarm optimization (PSO) demonstrated that R170 and R1270 achieved the best performance with a total energy efficiency of approximately 70% and a PUE of 1.1. Under the optimized conditions, 1.7 MW of cryogenic exergy can be recovered by integrating ORC and cooling loops, improving data center PUE by up to 36% and recovering approximately 10% of available exergy. These results suggest a promising pathway for reducing the electrical burden and advancing the sustainable development of both digital and hydrogen infrastructures. T-s and exergy flow diagram of integrated system using R170 as working fluidT-s and exergy flow diagram of integrated system using R1270 as working fluid

Authors

Institutions

Publication Details

Journal
Case Studies in Thermal Engineering
Published
2025-12-19
DOI
https://doi.org/10.1016/j.csite.2025.107571
Primary Topic
Thermodynamic and Exergetic Analyses of Power and Cooling Systems
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Integration of cryogenic exergy from liquid hydrogen into data center operation using an organic Rankine cycle

Chan Ho Chu, Si Hyung Park, Cheolhee Lee, Seung‐Ho Ryu et al.
Case Studies in Thermal Engineering
Thermodynamic and Exergetic Analyses of Power and Cooling Systems
article

Integration of cryogenic exergy from liquid hydrogen into data center operation using an organic Rankine cycle

Chan Ho Chu, Si Hyung Park, Cheolhee Lee, Seung‐Ho Ryu, Dong Kyu Kim, Minsung Kim, Do Hyun Lee, Jae Hyun Park
article en

Abstract

This study investigates the integration of cryogenic exergy of liquid hydrogen into data center power saving and cooling using an organic Rankine cycle (ORC). In the proposed system, the cryogenic exergy is first utilized for supplementary power generation and then for supplying low-temperature cooling, resulting in improved overall energy efficiency. Parametric analyses were conducted to evaluate the effects of hydrogen supply conditions on overall system performance. As the inlet temperature of liquid hydrogen decreased to 20 K, both the net power output and cooling capacity increased, reducing the power usage effectiveness (PUE) to 1.30. Increasing the mass flow rate of liquid hydrogen further improved the total energy efficiency to 69.2% and decreased the PUE to 1.14. Working fluid optimization using particle swarm optimization (PSO) demonstrated that R170 and R1270 achieved the best performance with a total energy efficiency of approximately 70% and a PUE of 1.1. Under the optimized conditions, 1.7 MW of cryogenic exergy can be recovered by integrating ORC and cooling loops, improving data center PUE by up to 36% and recovering approximately 10% of available exergy. These results suggest a promising pathway for reducing the electrical burden and advancing the sustainable development of both digital and hydrogen infrastructures. T-s and exergy flow diagram of integrated system using R170 as working fluidT-s and exergy flow diagram of integrated system using R1270 as working fluid

Case Studies in Thermal EngineeringVol. 77
Korea Electric Power Corporation (South Korea) (KR), Chung-Ang University (KR)
Openalex Percentile: Top 58%
Thermodynamic and Exergetic Analyses of Power and Cooling Systems
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.