Liquid CO2 fire suppression in liquor warehouses: A full-scale experimental study
Due to the inadequacy of existing fire suppression technologies in liquor warehouses, this study demonstrates the applicability of liquid CO 2 for extinguishing high-proof liquor fires. Full-scale fire suppression experiments using liquid CO 2 were conducted. Results indicated a 100% fire extinguishing success rate across all tested scales (4–60 m 2 ). Under a valve opening of 28% (approximately 450 kg/min), the suppression time was between 17 and 56 seconds, with amount of liquid CO 2 agent ranges from 0.12m 3 ∼0.38m 3 (120∼356kg). Upon extinguishment, the O 2 concentration decreased to 11.4–12.5%, while the CO 2 concentration reached 17.8–22.6%. After successful fire suppression, the warehouse environment was fully restored within 10 minutes through ventilation, significantly accelerating operational recovery. The cooling rate of the liquid CO 2 system increased significantly with fire size expansion, demonstrating advantages in cooling and explosion suppression for large-scale, high-temperature fires. This study confirms the high efficacy and engineering applicability of liquid CO 2 in suppressing liquor warehouse fires, provides theoretical support for fire prevention, and addresses a technical gap in practical implementations within this field.
Authors
- Gang Bai
- Zaihua Yang
- Xueming Li (ORCID: https://orcid.org/0000-0003-1058-2799)
- Bing Chen (ORCID: https://orcid.org/0000-0001-9160-5643)
- Wei Wan (ORCID: https://orcid.org/0009-0002-0228-7458)
- Su Juan Wang
Institutions
- Ministry of Education of the People's Republic of China (CN)
- Liaoning Technical University (CN)
- China Academy of Safety Sciences and Technology (CN)
- Hua Medicine (China) (CN)
Publication Details
- Journal
- Case Studies in Thermal Engineering
- Published
- 2025-12-19
- DOI
- https://doi.org/10.1016/j.csite.2025.107559
- Primary Topic
- Fire dynamics and safety research
- Type
- article
- Field-Weighted Citation Impact
- 0.00