Control Method for Reducing Inrush Current in Open-End-Winding Tap-Switching Transformer with Compensating Inverter
A tap-switching transformer can serve as an effective voltage regulation circuit when used as a voltage compensator. However, it generates inrush currents because of the step changes in load voltage during tap switching. In this study, we propose an AC voltage regulation circuit that employs a series-compensating inverter to solve the tap-switching transformer problem. We connect a series-compensating inverter to supply high-quality power to the load. However, the load voltage changes in a step-wise manner during tap switching, causing an inrush current. Therefore, we propose an inrush current suppression method for the proposed circuit. The experimental results demonstrate that the tap-switching coordination control reduces the inrush current by 53.4% when compared with the case of the tap-switching transformer alone.
Authors
- Kenji Arimatsu
- Rin Chishiki
- Hitoshi Haga (ORCID: https://orcid.org/0000-0001-7429-9242)
- Yoichi Ito
Institutions
- Shizuoka University (JP)
- GS Yuasa (Japan) (JP)
Publication Details
- Journal
- IEEJ Journal of Industry Applications
- Published
- 2025-12-11
- DOI
- https://doi.org/10.1541/ieejjia.20250060
- Primary Topic
- Power Quality and Harmonics
- Type
- article
- Field-Weighted Citation Impact
- 0.00