The increasing penetration of inverter-based renewable generation has reduced rotational inertia in power systems worldwide, causing steeper frequency drops after severe contingencies and increasing the risk of load shedding. In the Honduran context, this study evaluates the dynamic response of the National Interconnected System (NIS) operating in island mode through detailed DIgSILENT PowerFactory simulations, explicitly incorporating the national Under-Frequency Load Shedding (UFLS) scheme. Five disturbance scenarios were analyzed, including generation losses of 100 MW, 200 MW, and 262 MW, to assess the frequency support provided by Battery Energy Storage Systems (BESSs) and Flywheel Energy Storage Systems (FESSs). Results show that, in the base case, frequency decreased to 55.3 Hz during a 200 MW loss, confirming the system’s high vulnerability. The integration of a 75 MW BESS improved frequency stability to 58.74 Hz, preventing UFLS activation, while a 320 MW equivalent FESS provided only short-term inertial support with limited effectiveness. Quantitatively, the BESS reduced the minimum frequency, delayed UFLS activation by approximately 3.5 s, and provided sustained support, whereas the FESS contributed mainly during the first 5 s of the disturbance. In the most severe contingency (262 MW generation loss), the combined operation of BESS and FESS prevented total system collapse, improving the frequency nadir to 58.6 Hz. These results confirm that BESS provides more robust and sustained frequency support than FESS under the analyzed conditions, highlighting its effectiveness for improving system stability in low-inertia networks such as Honduras. The findings offer useful insights for future studies on storage integration and frequency regulation strategies.

Authors

Institutions

Publication Details

Journal
Energies
Published
2025-11-29
DOI
https://doi.org/10.3390/en18236287
Citations
2
Primary Topic
Microgrid Control and Optimization
Type
article
Field-Weighted Citation Impact
2.43

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Application of Battery and Flywheel Energy Storage Systems for Frequency Regulation in the Honduran Power Grid

Jonathan Muñoz Tabora, Danae Tome-Amador, Cristopher Varela-Aguilera, Dennis A. Rivera-López
2 citations
Energies
Microgrid Control and Optimization
2.43
article

Application of Battery and Flywheel Energy Storage Systems for Frequency Regulation in the Honduran Power Grid

Jonathan Muñoz Tabora, Danae Tome-Amador, Cristopher Varela-Aguilera, Dennis A. Rivera-López
article en
2 citations

Abstract

The increasing penetration of inverter-based renewable generation has reduced rotational inertia in power systems worldwide, causing steeper frequency drops after severe contingencies and increasing the risk of load shedding. In the Honduran context, this study evaluates the dynamic response of the National Interconnected System (NIS) operating in island mode through detailed DIgSILENT PowerFactory simulations, explicitly incorporating the national Under-Frequency Load Shedding (UFLS) scheme. Five disturbance scenarios were analyzed, including generation losses of 100 MW, 200 MW, and 262 MW, to assess the frequency support provided by Battery Energy Storage Systems (BESSs) and Flywheel Energy Storage Systems (FESSs). Results show that, in the base case, frequency decreased to 55.3 Hz during a 200 MW loss, confirming the system’s high vulnerability. The integration of a 75 MW BESS improved frequency stability to 58.74 Hz, preventing UFLS activation, while a 320 MW equivalent FESS provided only short-term inertial support with limited effectiveness. Quantitatively, the BESS reduced the minimum frequency, delayed UFLS activation by approximately 3.5 s, and provided sustained support, whereas the FESS contributed mainly during the first 5 s of the disturbance. In the most severe contingency (262 MW generation loss), the combined operation of BESS and FESS prevented total system collapse, improving the frequency nadir to 58.6 Hz. These results confirm that BESS provides more robust and sustained frequency support than FESS under the analyzed conditions, highlighting its effectiveness for improving system stability in low-inertia networks such as Honduras. The findings offer useful insights for future studies on storage integration and frequency regulation strategies.

EnergiesVol. 18(23)
National Autonomous University of Honduras (HN)
Universidad Nacional Autonoma de Honduras
Openalex Percentile: Top 9%
Microgrid Control and Optimization
2.43
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.