Reverse osmosis treatment of blow-down water for beneficial reuse and sustainable power generation

Reverse osmosis (RO) has been widely adopted for the treatment of blow-down water to facilitate sustainable water management in thermal power plants. This study investigates membrane fouling in a packaged RO system treating blow-down water to identify the causes of permeate flux decline and develop mitigation strategies. Results from blow-down water analysis, autopsy of the used membrane, and filtration experiments indicate that the RO system was likely under-designed with water recovery exceeding the design limit, creating conditions favourable for flux deterioration. Silica, present in blow-down water at high concentrations (∼50 mg/L), was identified as the dominant and most challenging membrane fouling culprit. Given the sulphate concentrations of 55–88 mg/L, barium sulphate scaling might also occur; however, the evidence was inconclusive. Unlike silica scaling, barium sulphate could be mitigated through appropriate anti-scalant dosing. The filtration experiments indicate that besides fouling, membrane compaction partially contributed to flux decline. Finally, WAVE simulation results suggest key strategies (e.g. lower water recovery, using larger membrane surface area or membrane with improved flux stability, increasing feed water temperature (up to 35 °C), blending with silica-free water sources, and optimising anti-scalant dosing) to enhance RO system water recovery while effectively avert membrane fouling. • Analysis of an RO system to treat & recycle blow-down water from a power station. • Silica was the predominant foulant in RO treatment of blow-down water. • Techniques were recommended to remediate membrane scaling. • According to computer simulation, recommended techniques can eliminate scaling.

Authors

Publication Details

Journal
Case Studies in Chemical and Environmental Engineering
Published
2025-12-03
DOI
https://doi.org/10.1016/j.cscee.2025.101306
Primary Topic
Membrane Separation Technologies
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Reverse osmosis treatment of blow-down water for beneficial reuse and sustainable power generation

Hung Cong Duong, Claudio Kohn, Long D. Nghiem, Viet Quang Ly
Case Studies in Chemical and Environmental Engineering
Membrane Separation Technologies
article

Reverse osmosis treatment of blow-down water for beneficial reuse and sustainable power generation

Hung Cong Duong, Claudio Kohn, Long D. Nghiem, Viet Quang Ly
article en

Abstract

Reverse osmosis (RO) has been widely adopted for the treatment of blow-down water to facilitate sustainable water management in thermal power plants. This study investigates membrane fouling in a packaged RO system treating blow-down water to identify the causes of permeate flux decline and develop mitigation strategies. Results from blow-down water analysis, autopsy of the used membrane, and filtration experiments indicate that the RO system was likely under-designed with water recovery exceeding the design limit, creating conditions favourable for flux deterioration. Silica, present in blow-down water at high concentrations (∼50 mg/L), was identified as the dominant and most challenging membrane fouling culprit. Given the sulphate concentrations of 55–88 mg/L, barium sulphate scaling might also occur; however, the evidence was inconclusive. Unlike silica scaling, barium sulphate could be mitigated through appropriate anti-scalant dosing. The filtration experiments indicate that besides fouling, membrane compaction partially contributed to flux decline. Finally, WAVE simulation results suggest key strategies (e.g. lower water recovery, using larger membrane surface area or membrane with improved flux stability, increasing feed water temperature (up to 35 °C), blending with silica-free water sources, and optimising anti-scalant dosing) to enhance RO system water recovery while effectively avert membrane fouling. • Analysis of an RO system to treat & recycle blow-down water from a power station. • Silica was the predominant foulant in RO treatment of blow-down water. • Techniques were recommended to remediate membrane scaling. • According to computer simulation, recommended techniques can eliminate scaling.

Case Studies in Chemical and Environmental EngineeringVol. 13
Openalex Percentile: Top 65%
Membrane Separation Technologies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.