Impact of integrating large scale solar photovoltaic on the voltage stability of the Nigeria power network

Abstract Integration of electricity based on intermittent renewable sources such as solar power to a grid can have adverse effect on electric power grid. In this work, we investigated the impact of integration of solar photovoltaic (SPV) on voltage stability. Six transmission buses (Kano, Kaduna, Gwagwalada, New Haven, Birnin Kebbi and Lokoja) with shortest distance to each of the 13 proposed locations have been identified and each of the Solar PV farms was integrated to the transmission bus closest to the proposed solar farm sites. The effects of SPV integration on Transmission lines loading have been performed and the Nigeria 56-bus transmission network was used for the investigation. Voltage stability analysis was carried out using the load margin obtained from the PV curve at each of the six identified buses and effect of SPV integration on the system voltage profile was identified. Sensitivity analysis was also performed in order to obtain the impact of increasing penetration on the voltage stability. The investigation was conducted using DigSilent Power Factory and MATLAB. The result shows that the safe region of integration for the six identified transmission buses is between 10 % (365.8 MW) at Gwagwalada bus and 19 % (695 MW) of base load power at Kaduna. 1 % of SPV was integrated simultaneously at Egbin, Ikeja West, Akangba, Sakete, Kano, Aja, Alagbon, and Osogbo with voltages lesser than 0.95 pu at the base case and the result reveals that all the buses in the system are within acceptable voltage level of 0.95–1.05 pu. Highest improvement in load margin is achieved when 1 % SPV is integrated at Kaduna bus among the six transmission buses considered. Different locations affect system load margins and voltage stability differently. 1 % integration of SPV at different buses significantly improve the load margin from 1,107.7 MW (Birnin Kebbi) to 1,448.9 MW (Kaduna).

Authors

Institutions

Publication Details

Journal
International Journal of Emerging Electric Power Systems
Published
2025-12-02
DOI
https://doi.org/10.1515/ijeeps-2025-0127
Primary Topic
Optimal Power Flow Distribution
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Impact of integrating large scale solar photovoltaic on the voltage stability of the Nigeria power network

Adedayo A. Yusuff, Thapelo Mosetlhe, T.R. Ayodele, Chaoran Liu et al.
International Journal of Emerging Electric Power Systems
Optimal Power Flow Distribution
article

Impact of integrating large scale solar photovoltaic on the voltage stability of the Nigeria power network

Adedayo A. Yusuff, Thapelo Mosetlhe, T.R. Ayodele, Chaoran Liu, Yuming Feng, Richard Oladayo Olarewaju, A.S.O. Ogunjuyigbe
article en

Abstract

Abstract Integration of electricity based on intermittent renewable sources such as solar power to a grid can have adverse effect on electric power grid. In this work, we investigated the impact of integration of solar photovoltaic (SPV) on voltage stability. Six transmission buses (Kano, Kaduna, Gwagwalada, New Haven, Birnin Kebbi and Lokoja) with shortest distance to each of the 13 proposed locations have been identified and each of the Solar PV farms was integrated to the transmission bus closest to the proposed solar farm sites. The effects of SPV integration on Transmission lines loading have been performed and the Nigeria 56-bus transmission network was used for the investigation. Voltage stability analysis was carried out using the load margin obtained from the PV curve at each of the six identified buses and effect of SPV integration on the system voltage profile was identified. Sensitivity analysis was also performed in order to obtain the impact of increasing penetration on the voltage stability. The investigation was conducted using DigSilent Power Factory and MATLAB. The result shows that the safe region of integration for the six identified transmission buses is between 10 % (365.8 MW) at Gwagwalada bus and 19 % (695 MW) of base load power at Kaduna. 1 % of SPV was integrated simultaneously at Egbin, Ikeja West, Akangba, Sakete, Kano, Aja, Alagbon, and Osogbo with voltages lesser than 0.95 pu at the base case and the result reveals that all the buses in the system are within acceptable voltage level of 0.95–1.05 pu. Highest improvement in load margin is achieved when 1 % SPV is integrated at Kaduna bus among the six transmission buses considered. Different locations affect system load margins and voltage stability differently. 1 % integration of SPV at different buses significantly improve the load margin from 1,107.7 MW (Birnin Kebbi) to 1,448.9 MW (Kaduna).

International Journal of Emerging Electric Power Systems
University of South Africa (ZA), University of Ibadan (NG), African Leadership Institute (ZA), Chongqing Three Gorges University (CN), Hangzhou Dianzi University (CN)
Openalex Percentile: Top 62%
Optimal Power Flow Distribution
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.