Modeling, analysis, and experimental validation of a swash plate compressor for automotive air conditioning

This paper presents a comprehensive study of a swash plate compressor, integrating both theoretical modeling and experimental validation. A mathematical model is developed to precisely describe the swash plate's motion and to derive the average power input to the compressor. This derivation considers the compressor's geometric parameters and angular speed under various operating conditions. Complementary to the theoretical analysis, an experimental investigation of an automotive air conditioning system equipped with a swash plate compressor was conducted. Both theoretical and experimental findings consistently demonstrate that the average power consumed by the swash plate compressor is primarily dependent on the swash plate inclination angle, rotational speed, and system pressure. A key conclusion drawn from this research is the critical importance of a small swash plate inclination angle. Such an angle is shown to be essential for minimizing power losses attributed to friction between the slipper and the swash plate, thereby reducing the overall shaft power required by the compressor. Furthermore, for design scenarios demanding both a long stroke and minimal shaft power for the swash plate compressor, the present analysis provides a crucial framework for selecting the optimal inclination angle and stroke length. Experimental results indicate that achieving high coefficients of performance (COP) and volumetric efficiencies necessitates low rotational speeds, high cooling capacities, and a reduced shaft power per unit mass flow rate of refrigerant. The coefficient of performance relative to the corresponding Carnot cycle is observed to decrease hyperbolically with an increase in the shaft power per unit mass flow rate of refrigerant. Importantly, the calculated shaft power values from the theoretical model provides a reasonable approximations agreement with those obtained from a simulation program developed by the compressor's manufacturer [8] across various operating conditions.

Authors

Institutions

Publication Details

Journal
Scientific Reports
Published
2025-11-29
DOI
https://doi.org/10.1038/s41598-025-27318-w
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Modeling, analysis, and experimental validation of a swash plate compressor for automotive air conditioning

Mohamad Abdel-Aal, Rabab Mohammed, Hany A. Mohamed
Scientific Reports
Refrigeration and Air Conditioning Technologies
article

Modeling, analysis, and experimental validation of a swash plate compressor for automotive air conditioning

Mohamad Abdel-Aal, Rabab Mohammed, Hany A. Mohamed
article en

Abstract

This paper presents a comprehensive study of a swash plate compressor, integrating both theoretical modeling and experimental validation. A mathematical model is developed to precisely describe the swash plate's motion and to derive the average power input to the compressor. This derivation considers the compressor's geometric parameters and angular speed under various operating conditions. Complementary to the theoretical analysis, an experimental investigation of an automotive air conditioning system equipped with a swash plate compressor was conducted. Both theoretical and experimental findings consistently demonstrate that the average power consumed by the swash plate compressor is primarily dependent on the swash plate inclination angle, rotational speed, and system pressure. A key conclusion drawn from this research is the critical importance of a small swash plate inclination angle. Such an angle is shown to be essential for minimizing power losses attributed to friction between the slipper and the swash plate, thereby reducing the overall shaft power required by the compressor. Furthermore, for design scenarios demanding both a long stroke and minimal shaft power for the swash plate compressor, the present analysis provides a crucial framework for selecting the optimal inclination angle and stroke length. Experimental results indicate that achieving high coefficients of performance (COP) and volumetric efficiencies necessitates low rotational speeds, high cooling capacities, and a reduced shaft power per unit mass flow rate of refrigerant. The coefficient of performance relative to the corresponding Carnot cycle is observed to decrease hyperbolically with an increase in the shaft power per unit mass flow rate of refrigerant. Importantly, the calculated shaft power values from the theoretical model provides a reasonable approximations agreement with those obtained from a simulation program developed by the compressor's manufacturer [8] across various operating conditions.

Scientific ReportsVol. 15(1)
Modern Academy (EG), Assiut University (EG)
Openalex Percentile: Top 61%
Refrigeration and Air Conditioning Technologies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.