Investigation of reduction in refrigerant charge for domestic split air conditioner

Abstract This study analyses the vapor compression cycle for the reduction of refrigerant charge without affecting the cooling capacity and COP. Globally, use of natural refrigerants is increasing. HC-290 is a possible refrigerant. HC-290 is highly flammable and is classified under A-3 safety class. Charge reduction below the safe operating limit is the requirement. The condenser carries majority of the charge in the vapour compression cycle. (VCC) Improvement in condenser internal volume by the change in flow direction by modifying the condenser orientation indicates a potential method for charge reduction. Analysis is carried out for a falling film condenser (FFC) for the use of HC-290 refrigerant in split type air conditioner (STAC) of cooling capacity of 5000 W complying the flammability limit as per international standard. Analytical calculations for the FFC and the CFD simulation for the falling film condensation has verified charge reduction. An experimental set up with same condenser tube was built. Number of condenser tubes in service were different compared to standard STAC condenser. At different operating conditions cooling capacity was monitored. The VCC process parameters were measured and cooling capacity, power consumption and coefficient of performance (COP) were calculated. When the 25% condenser tubes were not in service compared to all tubes in service, cooling capacity reduced by 2% compared to baseline cooling capacity. The energy consumed was marginally reduced so higher COP was observed. The charge reduction of 45 g is observed with near to no compromise on cooling capacity.

Authors

Institutions

Publication Details

Journal
International Journal of Air-Conditioning and Refrigeration
Published
2025-11-27
DOI
https://doi.org/10.1007/s44189-025-00086-y
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Investigation of reduction in refrigerant charge for domestic split air conditioner

Heramb C. Phadake, Kundlik V. Mali
International Journal of Air-Conditioning and Refrigeration
Refrigeration and Air Conditioning Technologies
article

Investigation of reduction in refrigerant charge for domestic split air conditioner

Heramb C. Phadake, Kundlik V. Mali
article en

Abstract

Abstract This study analyses the vapor compression cycle for the reduction of refrigerant charge without affecting the cooling capacity and COP. Globally, use of natural refrigerants is increasing. HC-290 is a possible refrigerant. HC-290 is highly flammable and is classified under A-3 safety class. Charge reduction below the safe operating limit is the requirement. The condenser carries majority of the charge in the vapour compression cycle. (VCC) Improvement in condenser internal volume by the change in flow direction by modifying the condenser orientation indicates a potential method for charge reduction. Analysis is carried out for a falling film condenser (FFC) for the use of HC-290 refrigerant in split type air conditioner (STAC) of cooling capacity of 5000 W complying the flammability limit as per international standard. Analytical calculations for the FFC and the CFD simulation for the falling film condensation has verified charge reduction. An experimental set up with same condenser tube was built. Number of condenser tubes in service were different compared to standard STAC condenser. At different operating conditions cooling capacity was monitored. The VCC process parameters were measured and cooling capacity, power consumption and coefficient of performance (COP) were calculated. When the 25% condenser tubes were not in service compared to all tubes in service, cooling capacity reduced by 2% compared to baseline cooling capacity. The energy consumed was marginally reduced so higher COP was observed. The charge reduction of 45 g is observed with near to no compromise on cooling capacity.

International Journal of Air-Conditioning and RefrigerationVol. 33(1)
MIT World Peace University (IN)
Openalex Percentile: Top 62%
Refrigeration and Air Conditioning Technologies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Investigation of reduction in refrigerant charge for domestic split air conditioner — Heramb C. Phadake, Kundlik V. Mali · International Journal of Air-Conditioning and Refrigeration (2025) | TGRS Research Map | TGRS