Experimental Studies of the Entry and Accumulation of Carbon Monoxide into Indoor Air in Case of Violation of the Removal of Combustion Products from Gas-Using Equipment

Statement of the problem. Combustion of gas fuel is accompanied by the formation of smoke gases containing carbon monoxide. Smoke gases must be completely removed through the flue ducts. Failure of the smoke ducts leads to the entry and accumulation of carbon monoxide in the premises, which negatively affects human well-being and health and can cause irreparable harm to health. To determine the conditions for the entry and accumulation of carbon monoxide in the air of the premises, it is necessary to conduct experimental studies of draft disruptions in the smoke duct during the operation of gas-using equipment. Results. Experimental studies of the entry and accumulation of carbon monoxide in the premises during the operation of a water heater with an open combustion chamber under conditions of draft disruption and the formation of reverse draft in the smoke duct during the removal of combustion products from the gas-using equipment were conducted. The conditions for the operation of the existing automatic safety system were determined. Conclusions. As a result of the conducted experimental studies it was established that when the draft in the smoke duct is disrupted (50 and 100 percent overlap of the smoke duct) the content of carbon monoxide in the room increases, the safety automation switches off the gas supply to the burner, limiting the accumulation of gas above the maximum permissible concentration in the air of the room. When modeling the reverse draft in the smoke duct, a range of reverse flow speeds was noted, amounting to from 3.5 to 4 m per sec, causing the entry and accumulation of carbon monoxide in the air of the premises, in an amount exceeding the norms of the maximum permissible concentration.

Authors

Institutions

Publication Details

Journal
Russian Journal of Building Construction and Architecture
Published
2025-11-13
DOI
https://doi.org/10.36622/2542-0526.2025.68.4.003
Primary Topic
Aerospace, Electronics, Mathematical Modeling
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Experimental Studies of the Entry and Accumulation of Carbon Monoxide into Indoor Air in Case of Violation of the Removal of Combustion Products from Gas-Using Equipment

A. O. Khomutov, Н. Н. Осипова, М.N. Goryunova
Russian Journal of Building Construction and Architecture
Aerospace, Electronics, Mathematical Modeling
article

Experimental Studies of the Entry and Accumulation of Carbon Monoxide into Indoor Air in Case of Violation of the Removal of Combustion Products from Gas-Using Equipment

A. O. Khomutov, Н. Н. Осипова, М.N. Goryunova
article en

Abstract

Statement of the problem. Combustion of gas fuel is accompanied by the formation of smoke gases containing carbon monoxide. Smoke gases must be completely removed through the flue ducts. Failure of the smoke ducts leads to the entry and accumulation of carbon monoxide in the premises, which negatively affects human well-being and health and can cause irreparable harm to health. To determine the conditions for the entry and accumulation of carbon monoxide in the air of the premises, it is necessary to conduct experimental studies of draft disruptions in the smoke duct during the operation of gas-using equipment. Results. Experimental studies of the entry and accumulation of carbon monoxide in the premises during the operation of a water heater with an open combustion chamber under conditions of draft disruption and the formation of reverse draft in the smoke duct during the removal of combustion products from the gas-using equipment were conducted. The conditions for the operation of the existing automatic safety system were determined. Conclusions. As a result of the conducted experimental studies it was established that when the draft in the smoke duct is disrupted (50 and 100 percent overlap of the smoke duct) the content of carbon monoxide in the room increases, the safety automation switches off the gas supply to the burner, limiting the accumulation of gas above the maximum permissible concentration in the air of the room. When modeling the reverse draft in the smoke duct, a range of reverse flow speeds was noted, amounting to from 3.5 to 4 m per sec, causing the entry and accumulation of carbon monoxide in the air of the premises, in an amount exceeding the norms of the maximum permissible concentration.

Russian Journal of Building Construction and Architecture(4(68))
Yuri Gagarin State Technical University of Saratov (RU), VolgoUralNIPIgaz (Russia) (RU)
Openalex Percentile: Top 67%
Aerospace, Electronics, Mathematical Modeling
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Experimental Studies of the Entry and Accumulation of Carbon Monoxide into Indoor Air in Case of Violation of the Removal of Combustion Products from Gas-Using Equipment — A. O. Khomutov, Н. Н. Осипова, et al. · Russian Journal of Building Construction and Architecture (2025) | TGRS Research Map | TGRS