A Study on the Possibility and Countermeasures of Sub Synchronous Oscillation in Korea Power Grid

On April 28, 2025, Spain experienced Sub-Synchronous Oscillation (SSO) caused by high penetration of inverter-based renewable energy in a weak grid environment with low Short Circuit Ratio (SCR), along with a blackout. This study simulates a comparable event in the Korean power grid using PSS/E. A three-phase fault in the Anjwa region resulted in voltage oscillations. After the voltage exceeded 1.1 pu, which led to the tripping of 6 GW of renewable generation, the frequency dropped below 59.3 ㎐, causing a further 4.5 GW of renewable generation to disconnect. STATCOM and GFM-ESS were implemented to mitigate voltage oscillations through dynamic reactive power support. Further analysis using PSCAD on a simplified grid revealed that the Power Plant Controller (PPC), combining VQ and PF control, effectively resolved the oscillation problem.

Authors

Publication Details

Journal
The Transactions of The Korean Institute of Electrical Engineers
Published
2025-11-11
DOI
https://doi.org/10.5370/kiee.2025.74.11.1810
Primary Topic
Power System Optimization and Stability
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

A Study on the Possibility and Countermeasures of Sub Synchronous Oscillation in Korea Power Grid

Jong-Ho Maeng, Kyeon Hur, Yoon-Sung Cho, Sang-Ho Park et al.
The Transactions of The Korean Institute of Electrical Engineers
Power System Optimization and Stability
article

A Study on the Possibility and Countermeasures of Sub Synchronous Oscillation in Korea Power Grid

Jong-Ho Maeng, Kyeon Hur, Yoon-Sung Cho, Sang-Ho Park, Jeong-Hoon Shin
article en

Abstract

On April 28, 2025, Spain experienced Sub-Synchronous Oscillation (SSO) caused by high penetration of inverter-based renewable energy in a weak grid environment with low Short Circuit Ratio (SCR), along with a blackout. This study simulates a comparable event in the Korean power grid using PSS/E. A three-phase fault in the Anjwa region resulted in voltage oscillations. After the voltage exceeded 1.1 pu, which led to the tripping of 6 GW of renewable generation, the frequency dropped below 59.3 ㎐, causing a further 4.5 GW of renewable generation to disconnect. STATCOM and GFM-ESS were implemented to mitigate voltage oscillations through dynamic reactive power support. Further analysis using PSCAD on a simplified grid revealed that the Power Plant Controller (PPC), combining VQ and PF control, effectively resolved the oscillation problem.

The Transactions of The Korean Institute of Electrical EngineersVol. 74(11)
Openalex Percentile: Top 67%
Power System Optimization and Stability
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.