Research on a Degradation Identification Method for GIS UHF Partial Discharge Sensors Based on S-Parameters
The ultra-high-frequency (UHF) detection method is highly accurate and has a fault localization function. At present, most gas-insulated switchgear (GIS) installations are equipped with online UHF monitoring devices to detect partial discharges. In order to ensure the accuracy of the detection results, UHF sensors need to be verified regularly. UHF sensors used for online monitoring are usually installed at the handhole of the GIS and cannot be removed. Measuring the laboratory verification indexes (e.g., equivalent height, dynamic range, etc.) of the sensors directly is very difficult. However, it is easier to measure <i>S</i><sub>11</sub> of the sensor for verification and <i>S</i><sub>21</sub> between it and the neighboring sensors by injecting power signals. Accordingly, this paper proposes a degradation identification method for GIS UHF sensors using a cross-comparison of <i>S</i>-parameters. When sensor sensitivity decreases, <i>S</i><sub>11</sub> increases while <i>S</i><sub>21</sub> decreases, both serving as effective indicators of performance degradation. In this study, the equivalent <i>S</i>-parameter network and the variation mechanisms of <i>S</i><sub>11</sub> and <i>S</i><sub>21</sub> during sensor verification were first analyzed. Normal and typically degraded sensor models were then constructed and coupled in different GIS structures for electromagnetic simulation. The simulation and on-site verification results show that <i>S</i><sub>11</sub> is mainly affected by the sensor's intrinsic performance and installation conditions at the inspection port, whereas <i>S</i><sub>21</sub> is predominantly influenced by sensor performance and the propagation characteristics of the GIS structure. Through cross-comparison of <i>S</i><sub>11</sub> and <i>S</i><sub>21</sub> at corresponding positions across three phases, sensor aging or failure can be effectively identified, enabling rapid on-site verification without removing the sensors. The proposed method was successfully validated on actual GIS equipment at the China Southern Power Grid Research Institute. It exhibits high accuracy, efficiency, and strong engineering applicability, enabling the early detection of degraded sensors and providing valuable support for condition assessment and maintenance decision-making in GIS online monitoring systems.
Authors
- Xiaoguo Chen (ORCID: https://orcid.org/0000-0002-0876-6495)
- Haotian Tan (ORCID: https://orcid.org/0000-0001-8698-0115)
- Tienan Cao
- Fuzeng Zhang (ORCID: https://orcid.org/0000-0002-3715-0366)
- Yufei Cui
- Kai Liu (ORCID: https://orcid.org/0009-0000-5442-4683)
- Lujia Wang (ORCID: https://orcid.org/0000-0003-2726-0593)
- Wei Lu (ORCID: https://orcid.org/0009-0004-5709-4164)
Institutions
- China University of Mining and Technology (CN)
- China Southern Power Grid (China) (CN)
Publication Details
- Journal
- Sensors
- Published
- 2025-11-10
- DOI
- https://doi.org/10.3390/s25226860
- Citations
- 1
- Primary Topic
- High voltage insulation and dielectric phenomena
- Type
- article
- Field-Weighted Citation Impact
- 0.52
Funders
- China University of Mining and Technology