A wet-bulb temperature-adaptive sequencing strategy for hospital chiller plants: Integrating Gordon-Ng and ε-NTU models to optimize energy consumption
Researchers investigated the characteristics and operation of chiller plants in inpatient buildings in southwestern China. The GN (Gordon-Ng) chiller model and ε- NTU cooling tower model to calculate the maximum cooling capacity of the chiller with wet bulb temperature as input. Two optimization strategies were proposed: Strategy-Y1, which considers the optimal energy efficiency range, and Strategy-Y2, which takes into account the outdoor wet bulb temperature. A case study was conducted on an inpatient building in Chengdu. The operating data of the chiller plants( energy consumption (kW), evaporator water supply temperature (°C), evaporator water flow rate (kg/s), etc.) were collected as experimental input parameters, and the COP-PLR curve of the chiller was regressed. Simulation results showed that the energy consumption effects of chillers and chiller plants in Strategy-Y1 were reduced by 3.72% and 2.93%, respectively. Thus, Strategy-Y2 can save the energy consumption of chiller and chiller plants by 10.92% and 8.68% respectively.
Authors
- Miaocheng Weng (ORCID: https://orcid.org/0000-0003-2792-998X)
- enyan Wang
- Xinyu Chen (ORCID: https://orcid.org/0000-0002-2132-2186)
- Fang Liu (ORCID: https://orcid.org/0000-0002-4646-7875)
- Yuan Yang (ORCID: https://orcid.org/0000-0002-3481-8447)
Institutions
- Chongqing University (CN)
- Sichuan Provincial Architectural Design and Research Institute (China) (CN)
Publication Details
- Journal
- Case Studies in Thermal Engineering
- Published
- 2025-11-08
- DOI
- https://doi.org/10.1016/j.csite.2025.107368
- Citations
- 1
- Primary Topic
- Building Energy and Comfort Optimization
- Type
- article
- Field-Weighted Citation Impact
- 1.01