Thermodynamic analysis of the refrigeration cycle of a domestic freezer with an electronic expansion valve

• EEV behaviour in domestic refrigeration cycles under varying conditions. • Discussion of operating domestic EEV systems near thermodynamic optimum. • Thermodynamic optimum requires HX outlet near refrigerant phase boundary. • EEV enables efficient operation at 32 °C and 16 °C ambient temperature. Electronic expansion valves (EEVs) can improve the energy efficiency of domestic refrigerators by allowing the refrigeration cycle to operate closer to its thermodynamic optimum across a wide range of operating points — unlike traditional capillary tubes, which are optimized to a single design point. However, the component interactions under such varying conditions are highly complex, and understanding them is crucial for efficient operation. A 0D–1D in-house simulation model, validated against experimental data, was used to investigate the refrigeration cycle behaviour of a domestic freezer with an EEV. In this model, outlet conditions of evaporator and high-pressure side heat exchangers are not fixed but emerge from the cycle calculation. A total of 39 operating points were simulated with varying operating parameters, including compressor speed, fan speeds, EEV opening ratio and refrigerant charge. Energy consumption was evaluated, followed by an in-depth analysis of internal cycle behaviour. The results show that efficient operation is achieved when the heat exchangers operate near the refrigerant phase boundaries: saturated vapour at the evaporator outlet (vapour quality ≈ 1) and saturated liquid at the high-pressure side outlet after the heat loop (vapour quality ≈ 0). Deviation too far into the two-phase region significantly increases energy consumption, while superheating or subcooling has a smaller effect. For both 950 and 1250 rpm compressor speeds, as well as ambient temperatures of 16 and 32 °C, the EEV enabled efficient operation of the refrigeration cycle. These results may be useful for implementing EEVs in domestic refrigerators and developing EEV control strategies.

Authors

Institutions

Publication Details

Journal
International Journal of Refrigeration
Published
2025-11-06
DOI
https://doi.org/10.1016/j.ijrefrig.2025.11.005
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Thermodynamic analysis of the refrigeration cycle of a domestic freezer with an electronic expansion valve

J. T. Kummer, Kevin Wimmer, Raimund Almbauer, Michael Lang
International Journal of Refrigeration
Refrigeration and Air Conditioning Technologies
article

Thermodynamic analysis of the refrigeration cycle of a domestic freezer with an electronic expansion valve

J. T. Kummer, Kevin Wimmer, Raimund Almbauer, Michael Lang
article en

Abstract

• EEV behaviour in domestic refrigeration cycles under varying conditions. • Discussion of operating domestic EEV systems near thermodynamic optimum. • Thermodynamic optimum requires HX outlet near refrigerant phase boundary. • EEV enables efficient operation at 32 °C and 16 °C ambient temperature. Electronic expansion valves (EEVs) can improve the energy efficiency of domestic refrigerators by allowing the refrigeration cycle to operate closer to its thermodynamic optimum across a wide range of operating points — unlike traditional capillary tubes, which are optimized to a single design point. However, the component interactions under such varying conditions are highly complex, and understanding them is crucial for efficient operation. A 0D–1D in-house simulation model, validated against experimental data, was used to investigate the refrigeration cycle behaviour of a domestic freezer with an EEV. In this model, outlet conditions of evaporator and high-pressure side heat exchangers are not fixed but emerge from the cycle calculation. A total of 39 operating points were simulated with varying operating parameters, including compressor speed, fan speeds, EEV opening ratio and refrigerant charge. Energy consumption was evaluated, followed by an in-depth analysis of internal cycle behaviour. The results show that efficient operation is achieved when the heat exchangers operate near the refrigerant phase boundaries: saturated vapour at the evaporator outlet (vapour quality ≈ 1) and saturated liquid at the high-pressure side outlet after the heat loop (vapour quality ≈ 0). Deviation too far into the two-phase region significantly increases energy consumption, while superheating or subcooling has a smaller effect. For both 950 and 1250 rpm compressor speeds, as well as ambient temperatures of 16 and 32 °C, the EEV enabled efficient operation of the refrigeration cycle. These results may be useful for implementing EEVs in domestic refrigerators and developing EEV control strategies.

International Journal of RefrigerationVol. 181
Graz University of Technology (AT)
Openalex Percentile: Top 66%
Refrigeration and Air Conditioning Technologies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.